Step 7. Perform Detector Check
7.1 Air Flow
1. To verify sufficient sampling of ducted air, use a manom-
eter  to  measure  the  differential  pressure  created  from 
air flow across the sampling tubes. The pressure should 
measure no less than 0.01 inches of water and no greater 
than 1.20 inches of water.
2. To determine that smoke is capable of entering the sens-
ing chamber, conduct a visual examination to note any 
obscurations  around  the  sensing  chamber.  If  a  smoke 
test  is  required,  blow  smoke  from  a  cigarette,  cotton 
wick, or punk directly at the smoke detector head. It is 
important  to  plug  the  exhaust  and  sampling  tube  hole 
to  prevent  ducted  air  from  blowing  smoke  away  from 
the smoke detector head. Record all test records in the 
Detector Test Log at the end of this manual.
CAUTION
Remove  the  plugs  after  testing  or  the  detector  will  not 
sense smoke in the air duct.
7.2 Alarm Tests
Before replacing the duct housing cover, check the detector 
interconnections. Check the DH500ACDC as follows:
A. M02-04-00 Magnet Test
  1. Make sure power is applied to the detector.
  2. Position the painted surface of the test magnet against 
the housing next to the rib molded onto the outside of 
the housing (see Figure 7).
  3. The LEDs on the detector should latch on as should 
any  accessories  (PA400,  RA400ZA,  RTS451)  and  the 
alarm  condition  verified  at  the  control  panel.  The 
control panel must be active to initiate an alarm.
B. RTS451/RTS451KEY Remote Test Station
  The  RTS451/RTS451KEY  Remote  Test  Station  facili-
tates  testing  of  the  duct  detector  alarm  capability. 
The  DH500ACDC  duct  detector  cannot  be  reset  by  the 
RTS451/RTS451KEY. It must be reset at the system con-
trol panel.
To  install  the  RTS451/RTS451KEY  test  coil,  connect  the 
device as shown in Figure 9. Place the coil in the detector 
housing with the arrow facing up and pointing toward the 
detector as in Figure 9. Attach the coil leads to the housing 
terminals as shown; polarity is not important. Firmly screw 
the  test  coil  mounting  bracket  in  place  over  the  test  coil. 
The resistance of the wire connecting the remote test sta-
tion to the duct detector must be less than 25 ohms.
7.3 MOD400R Sensitivity Test
After verification of alarm capability, use a MOD400R test 
module  with  a  voltmeter  to  check  detector  sensitivity  as 
described in the MOD400R installation manual. The hous-
ing cover must be removed to perform this test.
If the MOD400R readings indicate that the sensor head is 
outside  of  the  acceptable  range,  the  sensor  heads  require 
cleaning (refer to Periodic Maintenance Requirements).
7.4 Trouble Test
The  capability  of  trouble  detection  is  tested  by  removing 
the  detector  head  from  the  duct  housing.  The  detector 
head  is  removed  by  rotating  it  counterclockwise  about 
10  degrees  (Figure  8).  The  system  control  panel  should 
indicate a trouble condition. Reinstalling the detector head 
should clear the trouble condition.
SAMPLING TUBE
FILTERS
SAMPLING TUBE
MOUNTING
SCREWS
DETECTOR HEAD
EXHAUST 
FILTER ADAPTER
DETECTOR BASE
INLET SAMPLING TUBE
FOAM GASKET
Figure 6. Sampling tube filter installation:
H0239-00
D500-07-00 
I56-432-11R