INSTALLATION – SOLAR STORAGE TANK 
28 
MAINS WATER SUPPLY 
Where the mains water supply pressure exceeds that shown in the table below, 
an approved pressure limiting valve is required and should be fitted as shown 
in the installation diagram 
 
Model 260 
Relief valve setting 
1000 kPa 
Expansion control valve setting * 
850 kPa 
Max. mains supply pressure 
 
With expansion control valve 
680 kPa 
Without expansion control valve 
800 kPa 
Min. mains supply pressure 
200 kPa 
 
* Expansion control valve not supplied with the water heater. 
 
 
TANK WATER SUPPLY 
If the water heater is supplied with water from a tank supply and a minimum 
water supply pressure of 200 kPa at the water heater cannot be achieved, then 
a pressure pump system must be installed to allow the solar circuit system to 
operate. Care must be taken to avoid air locks. The cold water line from the 
supply tank should be adequately sized and fitted with a full flow gate valve or 
ball valve.