4 -  8 
4. OPERATION 
 
4.2.2 Absolute value command system 
(1) Point table 
Set the point table values using the MR Configurator (servo configuration software) or from the 
operating section. 
Set the position data, motor speed, acceleration time constant, deceleration time constant, dwell and 
auxiliary function to the point table. The following table gives a setting example. 
Name Setting 
range Unit 
Description 
Position data 
999999 to 999999 
[ 10
STM
m] 
Set the target address (absolute value). 
This value can also be set using the teaching function. (Refer to section 
7.10.) 
The unit can be changed using feed length multiplication factor selection of 
parameter No. 1. 
Motor speed 
0 to permissible speed 
r/min 
Set the command speed of the servo motor for execution of positioning. 
The setting should be equal to or less than the instantaneous permissible 
speed of the servo motor. 
Acceleration 
time constant 
0 to 20000 
ms 
Set the acceleration time constant. 
Set the time until the rated speed of the servo motor is reached. 
Deceleration 
time constant 
0 to 20000 
ms 
Set the deceleration time constant. 
Set the time until the servo motor running at rated speed comes to a stop. 
Dwell 
0 to 20000 
ms 
Set the dwell. 
Set "0" in the auxiliary function to make the dwell invalid. 
Set "1" in the auxiliary function and 0 in the dwell to perform continuous 
operation. 
When the dwell is set, the position command of the selected point table is 
completed, and after the set dwell has elapsed, the position command of the 
next point table is started. 
Auxiliary 
function 
0   1 
 
Set the auxiliary function. 
0: Automatic operation is performed in accordance with a single point table 
chosen. 
1: Operation is performed in accordance with consecutive point tables 
without a stop. 
When a different rotation direction is set, smoothing zero (command 
output) is confirmed and the rotation direction is then reversed. 
Setting "1" in point table No.31 results in an error. 
For full information, refer to section 4.2.6. 
 
(2) Parameter setting  
Set the following parameters to perform automatic operation. 
(a) Command mode selection (parameter No.0) 
Select the absolute value command system. 
0
Absolute value command system
Parameter No. 0