Справочник Пользователя для Mitsubishi Electronics QD64D2

Скачать
Страница из 154
8
 - 9
8.9 When the Latch Counter Function Cannot be Executed
8.9.1 When the latch counter function cannot be executed by the latch counter execution command (Y07)
8
TROUBLESHOOTING
8.9
When the Latch Counter Function Cannot be Executed
8.9.1
When the latch counter function cannot be executed by the latch 
counter execution command (Y07)
8.9.2
When the latch counter function cannot be executed by the latch 
counter input terminal (LATCH)
8.10 When the Error Code (Un\G18)/Warning Code (Un\G19) 
Cannot be Reset
Table 8.16 When the latch counter function cannot be executed by the latch counter execution command (Y07)
Check item
Action
Reference
Is the ON and OFF time of the latch counter 
execution command (Y07) longer than 2ms?
Set the ON and OFF time 2ms or longer. 
Is the latch counter input terminal (LATCH) ON? 
Turn OFF the latch counter input terminal 
(LATCH). 
Table 8.17 When the latch counter function cannot be executed by the latch counter input terminal (LATCH)
Check item
Action
Reference
Is the external wiring of the latch counter input 
terminal (LATCH) correct?
Check the external wiring and correct the error. 
Is the latch counter execution command (Y07) 
ON? 
Turn OFF the latch counter execution command 
(Y07).
Table 8.18 When the error code (Un\G18)/warning code (Un\G19) cannot be reset
Check item
Action
Reference
Is the cause of the error/warning fixed? 
Refer to the description and action columns in error 
code and warning code list, and fix the cause. 
Is the ON and OFF time of the error reset 
command (Y0D) 2ms or longer. 
Set the ON and OFF time 2ms or longer.