8.11 Action and Handling of Errors
8.11.1 Error code list
8
TROUBLESHOOTING
Table 8.19 Error code list (continued)
Error 
code
Description
Action
Operation at error
Error channel
Other channels
31m
[Continuous comparison No.m execution not possible 
error]
Turn OFF the coincidence 
output test command, then turn 
ON the continuous comparison 
execution command.
The continuous 
comparison cannot 
be started. (The 
error does not 
affect the other 
continuous 
comparison 
number.)
The error does 
not affect other 
channels.
The continuous comparison No.m execution 
command (Y09 and Y0A) is turned ON while one of 
the following is ON. 
•Coincidence output No.1 test command (Y0B)
•Coincidence output No.2 test command (Y0C)
"m" indicates the continuous comparison number 
where the error occurred. 
500
[Ring counter upper/lower limit value setting error]
Set a value as follows. 
(Lower limit value 
 Upper limit 
value)
The ring counter 
function does not 
start counting. 
The count enable command (Y06) is turned ON 
under the following condition. 
(Ring counter lower limit value (Un\G0 and 1)) > 
(Ring counter upper limit value (Un\G2 and 3))
(Only for the ring counter function)
810
[Switch setting error]
Set a correct value in GX 
Developer and perform [Write to 
PLC]. After that, power OFF 
then ON the programmable 
controller CPU or reset it. (Refer 
to Section 4.5.)
•All functions and counting are 
stopped. 
•Updating the external I/O status 
monitor is stopped.
•The module READY (X00) turns 
OFF.
An invalid value is set in the switch setting for 
intelligent function module in GX Developer. 
820
[Programmable controller CPU error]
Power OFF then ON the 
programmable controller CPU or 
reset it.
An error occurred in the programmable controller 
CPU. 
830
[Watchdog timer error of programmable controller 
CPU]
A watchdog timer error occurred in the programmable 
controller CPU.
840
[Module error]
Power OFF then ON the 
programmable controller CPU or 
reset it.
If an error occurs again, replace 
the module.
An error occurred in the module.
850
[Hardware error]
Replace the module.
A hardware error occurred. 
860
[Blown fuse error]
•For replacement of fuse, please 
consult your local Mitsubishi 
representative.
•When temporarily using the 
module with a blown fuse, do 
not apply a voltage to the 
external coincidence output 
power supply terminal and 
power OFF then ON or reset 
the programmable controller 
CPU.
The fuse of the external coincidence output part is 
blown.