5. Peripheral Devices 
 
 
 
 
 
5 - 4
5-2  Selection of circuit protector and contactor 
 
Always select the circuit protector and contactor properly, and install them to each power supply unit to 
prevent disasters. 
 
5-2-1  Selection of circuit protector 
 
Select the circuit protector as in the expression below. 
 
Unit type 
MDS-R- 
V1-20 V1-40 V1-60 V1-80 
Recommended 
breaker 
(Mitsubishi Electric 
Corp.: option part)
 
NF30- 
CS3P-15A 
NF30- 
CS3P-20A
NF30- 
CS3P-30A
NF50- 
CW3P-40A
Rated current of the 
recommended 
breaker 
15A 20A 30A 40A 
 
Unit type 
MDS-R- 
V2-2020 V2-4020
V2-4040
V2-6040
V2-6060
V2-8040 V2-8060 V2-8080
Recommended 
breaker 
(Mitsubishi Electric 
Corp.: option part)
 
NF30- 
CS3P-20A 
NF30- 
CS3P-30A
NF30- 
CS3P-30A
NF30- 
CS3P-30A
NF50- 
CW3P-40A
NF50- 
CW3P-40A 
NF50- 
CW3P-40A 
NF50- 
CW3P-40A
Rated current of the 
recommended 
breaker 
20A 30A 30A 30A 40A 40A 40A 40A 
Option part: A breaker is not prepared as an NC unit accessory, so purchase the part from your dealer, etc.
 
 
 
 
CAUTION
 
1.  If a circuit protector is shared by several drive units, the circuit protector may 
not activate when a short-circuit fault occurs in a small capacity drive unit. This 
is dangerous, so never share the circuit protector by several drive units. 
Always install the circuit protector for each drive unit. 
2.  If the control power (CN22) must be protected, select according to the section 
"5-4 Selection of control power supply".