Справочник Пользователя для Mitsubishi Electronics MDS-R
7. Wiring and Connection
7 - 15
7-7-2 Contactor control signal (MC) output circuit
A relay or photo coupler can be driven. When using an inductive load, install a diode.
(Tolerable current: 40mA or less, rush current: 100mA or less)
(Tolerable current: 40mA or less, rush current: 100mA or less)
When using an internal power supply
When using an external power supply
Contactor
MDS-R-V1/V2
10
VDD
5
COM
15
MC
3
SG
CN9
Contactor control relay
(There are also types that
are built into the contactor.)
(There are also types that
are built into the contactor.)
24VDC
The servo drive unit will
fail if the diode polarity is
incorrect.
fail if the diode polarity is
incorrect.
Contactor
MDS-R-V1/V2
10
VDD
5
COM
15
MC
3
SG
CN9
27VDC
or less
or less
24VDC
Contactor control relay
(There are also types that
are built into the contactor.)
(There are also types that
are built into the contactor.)
The servo drive unit will
fail if the diode polarity is
incorrect.
fail if the diode polarity is
incorrect.
When using the internal power supply, the power can be directly connected to
VDD if using only the digital output (MC, MBR). When using the digital input
(EMGX), always connect across VDD-COM.
VDD if using only the digital output (MC, MBR). When using the digital input
(EMGX), always connect across VDD-COM.
POINT