7. Wiring and Connection 
 
 
 
 
 
7 - 16
7-7-3  Contactor power ON sequences 
 
When using the contactor control output (CN9 connector: MC) for the MDS-R-V1/V2 servo drive unit, 
the main circuit power supply is turned ON with the sequence shown below. In the 200ms interval after 
the drive unit emergency stop input is canceled, the contactor contact fusion is checked by discharging 
the PN bus voltage with the regenerative resistor. External contactor fusion (alarm 5F) is detected when 
the contactor has fusion. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Contactor power ON sequences 
ON 
OFF 
Ready ON signal (READY) 
ON 
OFF 
Servo ON signal (SERVO) 
0
500
1000
1500  Time (ms)
Command input enable
OFF 
ON 
Motor brake control output (MBR) 
Dynamic brake 
OFF 
ON 
PN bus voltage 
PN charging completion 
Motor ON (GATE) 
ON 
OFF 
Ready completion 
 
Emergency stop (EMG) 
OFF 
ON 
ON 
OFF 
Contactor control output (MC) 
 
 
7-7-4  Contactor shutoff sequences 
 
When an emergency stop or servo alarm occurs, the NC confirms the MC shutoff enabled (motor stop or 
dynamic brake operation) for all axes, and then shuts off the contactors. If an MC shutoff enabled signal 
is not output, the contactors will be forcibly shut off by the controlling unit after 30 seconds. 
 
1st axis 
(dynamic brake stop) 
2nd axis 
 (deceleration control) 
3rd axis 
  (deceleration control + 
drop prevention control) 
0
0
0
MC shutoff enable
Speed
MC shutoff enable
Speed
MC shutoff enable
Speed
Contactor control output (MC) 
ON
OFF
Drop prevention 
Shutoff after confirmation 
of all axes enable 
OFF
ON
Emergency stop (EMG) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Contactor shutoff sequences