Справочник Пользователя для Mitsubishi Electronics Q25HCPU

Скачать
Страница из 236
 
 
 
9 - 23                                                                                                                                                       9 - 23 
MELSEC-Q
 
9   LOADING AND INSTALLATION 
 
9.6 Wiring 
9.6.1 The precautions on the wiring 
!
 DANGER 
 Completely turn off the external power supply when installing or 
placing wiring. Not completely turning off all power could result in 
electric shock or damage to the product. 
 When turning on the power supply or operating the module after 
installation or wiring work, be sure that the module's terminal covers are 
correctly attached. Not attaching the terminal cover could result in 
electric shock. 
 
!
 CAUTION 
 Be sure to ground the FG terminals and LG terminals to the 
protective ground conductor. Not doing so could result in electric 
shock or erroneous operation. 
 When wiring in the PLC, be sure that it is done correctly by checking 
the product's rated voltage and the terminal layout. Connecting a 
power supply that is different from the rating or incorrectly wiring the 
product could result in fire or damage. 
 External connections shall be crimped or pressure welded with the 
specified tools, or correctly soldered. Imperfect connections could 
result in short circuit, fires, or erroneous operation. 
 Tighten the terminal screws with the specified torque. If the terminal screws 
are loose, it could result in short circuits, fire, or erroneous operation. 
Tightening the terminal screws too far may cause damages to the screws 
and/or the module, resulting in fallout, short circuits, or malfunction. 
 Be sure there are no foreign substances such as sawdust or wiring 
debris inside the module. Such debris could cause fires, damage, or 
erroneous operation. 
 The module has an ingress prevention label on its top to prevent 
foreign matter, such as wire offcuts, from entering the module during 
wiring. 
Do not peel this label during wiring. 
Before starting system operation, be sure to peel this label because 
of heat dissipation. 
 
The precautions on the connection of the power cables are described below. 
 
(1)   Power supply wiring 
(a) Separate the PLC's power supply line from the lines for I/O devices and 
power devices as shown below. 
When there is much noise, connect an insulation transformer. 
 
PLC
PLC power
supply
Main power
supply
I/O power supply
Main circuit device
I/O devices
Main circuit device
Insulation
transformer
200VAC
T1