9   LOADING AND INSTALLATION 
 
(b) Do not connect the 24VDC outputs of two or more power supply modules in 
parallel to supply power to one I/O module. Parallel connection will damage 
the power supply modules. 
 
24VDC
24VDC
24VDC
P
o
wer suppl
  
   
    
m
odul
e
P
o
wer suppl
m
odul
e
I/
O
 m
odul
e
I/
O
 m
odul
e
P
o
wer suppl
m
odul
e
External power supply
 
 
(c) 100VAC, 200VAC and 24VDC wires should be twisted as dense as possible. 
Connect the modules with the shortest distance. 
Also, to reduce the voltage drop to the minimum, use the thickest wires 
possible (maximum 2mm
2
). 
 
(d) Do not bundle the 100VAC and 24VDC wires with, or run them close to, the 
main circuit (high voltage, large current) and I/O signal lines. Reserve a 
distance of at least 100 mm from adjacent wires. 
 
(e) As a countermeasure to power surge due to lightening, connect a surge 
absorber for lightening as shown below. 
 
AC
E1
E2
Surge absorber for lightening
PLC
 
 
POINT 
 
(1) Separate the ground of the surge absorber for lightening (E1) from that of the 
PLC (E2). 
(2) Select a surge absorber for lightening whose power supply voltage does no 
exceed the maximum allowable circuit voltage even at the time of maximum 
power supply voltage elevation.