10 - 3                                                                                                                                                       10 - 3 
MELSEC-Q
 
10   MAINTENANCE AND INSPECTION 
 
10.2 Periodic Inspection 
The items that must be inspected one or two times every 6 months to 1 year are listed 
below. 
When the equipment is moved or modified, or layout of the wiring is changed, also 
perform this inspection. 
 
Periodic Inspection 
 
Item 
Inspection Item 
Inspection 
Judgment Criteria 
Remedy 
Ambient 
temperature 
0 to 55 °C 
Ambient humidity 
5 to 95 %RH  1 
Ambient env
ironment 
Atmosphere 
Measure with a thermometer 
and a hygrometer. 
Measure corrosive gas. 
Corrosive gas must not be 
present. 
When the sequencer is 
used in the board, the 
ambient temperature in 
the board becomes the 
ambient temperature. 
85 to 132VAC 
170 to 264VAC 
2 Power 
voltage 
Measure a voltage across the 
terminals of 100/200VAC and 
24VDC. 
15.6 to 31.2VDC 
Change the power 
supply. 
Looseness, rattling 
Move the module to check for 
looseness and rattling. 
The module must be installed 
fixedly. 
Further tighten screws. 
If the CPU, I/O, or power 
supply module is loose, 
fix it with screws. 
Installation  Adhesion of dirt and 
foreign matter 
Check visually. 
Dirt and foreign matter must 
not be present. 
Remove and clean. 
Looseness of 
terminal screws 
Try to further tighten screws 
with a screwdriver. 
Screws must not be loose. 
Further tighten. 
Proximity of 
solderless terminals 
to each other 
Check visually. 
Solderless terminals must be 
positioned at proper intervals. 
Correct. 
C
onnection 
Looseness of 
connectors 
Check visually. 
Connectors must not be loose. 
Further tighten connector 
fixing screws. 
5 Battery 
check on the monitor mode of 
the GX Developer that SM51 or 
SM52 is turned OFF. 
(Preventive maintenance) 
Even if the lowering of a 
battery capacity is not 
shown, replace the 
battery with a new one if 
a specified service life of 
the battery is exceeded. 
1 When AnS Series Module is included in the system, the judgement criteria will be from 10 to 90 % RH.