Справочник Пользователя для Mitsubishi Electronics Q25HCPU

Скачать
Страница из 236
 
 
 
10 - 5                                                                                                                                                       10 - 5 
MELSEC-Q
 
10   MAINTENANCE AND INSPECTION 
 
10.3.1 Battery life 
(1)   CPU module battery (Q6BAT) life 
(a) The CPU module battery life is given below. 
 
Battery life 
CPU Module 
Type 
Energization 
Time Ratio 
Guaranteed value 
(MIN) 
Value in actual use 
(TYP) 
After SM51 is energized 
(Guaranteed time after 
alarm occurrence) 
0% 5433hr 13120hr 
120hr 
30% 7761hr  18742hr 
120hr 
50% 10866hr  26240hr 
120hr 
70% 18110hr  43733hr 
120hr 
Q02CPU 
100% 10years  10years 
120hr 
0% 2341hr  6435hr 
120hr 
30% 3344hr  9192hr 
120hr 
50% 4682hr  12870hr 
120hr 
70% 7803hr  21450hr 
120hr 
Q02HCPU 
Q06HCPU 
100% 10years  10years 
120hr 
0% 1260hr  4228hr 
48hr 
30% 1800hr  6040hr 
48hr 
50% 2520hr  8456hr 
48hr 
70% 4200hr  14093hr 
48hr 
Q12HCPU 
Q25HCPU 
100% 10years  10years 
48hr 
1: The energization time ratio denotes the ratio of power-on time in a day (24 hours). 
(When power is on for 12 hours and off for 12 hours, the energization time ratio is 
50%.) 
 
(b) The Q6BAT life is 10 years when it is used without connecting to the CPU 
module. 
 
(2)   SRAM card battery life 
The SRAM card battery life changes depending on the combination of the serial 
number (first 5 digits) of the CPU module and the manufacturing control number 
of the memory card. 
The SRAM card battery life is indicated below. 
 
(a) CPU module whose serial number's first 5 digits are "04012" or later 
 
Battery life 
SRAM card 
Energization 
Time Ratio 
Guaranteed value 
(MIN) 
Value in actual use 
(TYP) 
After SM51 is energized 
(Guaranteed time after 
alarm occurrence) 
0% 690hr  6336hr 
8hr 
Q2MEM-1MBS 
Manufacturing 
control number 
"
A" 
100% 11784hr  13872hr 
8hr 
0% 2400hr  2.7years 
20hr 
30% 2880hr  3.6years 
20hr 
50% 4320hr  4.5years 
20hr 
70% 6480hr  5.0years 
20hr 
Q2MEM-1MBS 
Manufacturing 
control number 
"
B" 
100% 5.0years  5.0years 
50hr 
0% 2400hr  2.7years 
20hr 
30% 2880hr  3.6years 
20hr 
50% 4320hr  4.5years 
20hr 
70% 6480hr  5.0years 
20hr 
Q2MEM-2MBS 
100% 5.0years  5.0years 
50hr