4 - 3                                                                                                                                                       4 - 3 
MELSEC-Q
 
4   HARDWARE SPECIFICATION OF THE CPU MODULE 
 
Performance Specifications (continued) 
Model 
Item 
Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU 
Remark 
Link special relay [SB]  
2048 points (SB0 to 7FF) 
Link special register [SW]  
2048 points (SW0 to 7FF) 
Step relay [S]  
8192 points (S0 to 8191) 
Index register [Z]  
16 points (Z0 to 15) 
Pointer [P]  
4096 points (P0 to 4095), set parameter values to select usable range 
of in-file pointer / shared pointers. 
Interrupt pointer [ I ]  
256 points (I0 to 255) 
The specified intervals of the system interrupt pointers I28 to I31 can 
be set with parameters.(0.5 to 1000ms, 0.5 ms
/unit
Default   I28 : 100ms   I29 : 40ms   I30 : 20ms   I31 : 10ms 
Special relay [SM]  
2048 points (SM0 to 2047) 
Special register [SD]  
2048 points (SD0 to 2047) 
Function input [FX]  
16 points (FX0 to F) 
Function output [FY]  
16 points (FY0 to F) 
Num
ber of
 devi
c
e poi
nt
s
 
Function register[FD]  
5 points (FD0 to 4) 
The number of device 
points is fixed. 
Link direct device 
Device having a direct access to link device. 
MELSECNET/10(H) use only. 
Specified form : J
\X
, J
\Y
, J
\W
,  
J
\B
, J
\SW
, J
\SB
 
——
 
Intelligent function module device 
Device having a direct access to the buffer memory of the intelligent 
function module.  Specified form : U
\G
 
——
 
Latch (power failure compensation) range 
L0 to 8191 (default) 
(Latch range can be set for B, F, V, T, ST, C, D, and W.) 
Remote RUN/PAUSE contact 
RUN and PAUSE contacts can be set from among X0 to 1FFF, 
respectively. 
Set parameter values 
to specify 
Clock function 
Year, month, day, hour, minute, second, day of the week 
(leap year automatic distinction) 
Accuracy -3.18 to +5.25s (TYP. +2.12s) /d at 0°C 
Accuracy -3.93 to +5.25s(TYP. +1.90s)/d at 25°C 
Accuracy -14.69 to +3.53s(TYP. -3.67s)/d at 55°C 
——
 
Allowable momentary power failure period 
Varies according to the type of power supply module. 
——
 
5VDC internal current consumption 
0.60A 
0.64A 
0.64A 
0.64A 
0.64A 
——
 
H 98mm 
(3.86inch) 
——
 
W 27.4mm 
(1.08inch) 
——
 
External dimensions 
D 89.3mm 
(3.52inch) 
——
 
Weight 
0.20kg 0.20kg 0.20kg 0.20kg 0.20kg 
——