4 - 5                                                                                                                                                       4 - 5 
MELSEC-Q
 
4   HARDWARE SPECIFICATION OF THE CPU MODULE 
 
No. Name 
Application 
1)  Module fixing hook 
Hook used to fix the module to the base unit. (Single-motion installation) 
2) "Mode" 
LED 
Indicates the mode of the CPU module. 
ON (green) 
: Q mode 
ON (orange) 
: A mode 
Flicker (green)  : Enforced ON/OFF for external I/O registered 
3) "RUN" 
LED 
Indicates the operating status of the CPU module. 
ON 
: During operation in "RUN" status. 
OFF 
: During a stop in "STOP" status or detection of error whose occurrence stops 
operation. 
Flicker  : When parameter/program is written at STOP and RUN/STOP switch is 
changed from "STOP" to "RUN". 
To turn ON the RUN LED after writing the program, carry out the following 
steps. 
y Set the RUN/STOP switch from "RUN" 
→ "STOP" → "RUN". 
y Reset with the RESET/L.CLR switch. 
y Restart the PLC power. 
To turn ON the RUN LED after writing the parameters, carry out the following 
steps. 
y Reset with the RESET/L.CLR switch. 
y Restart the PLC power. 
(If the RUN/STOP switch is set from "RUN" 
→ "STOP" → "RUN" after 
changing the parameters, the parameters related to the intelligent function 
module, such as the network parameters, will not be reflected.) 
4) "ERR." 
LED 
ON 
: Detection of self-diagnosis error which will not stop operation, except battery 
error. 
(When operation continued at error detection is set in the parameter.) 
OFF : 
Normal 
Flicker  : Detection of error whose occurrence stops operation. 
When automatic write to standard ROM is completed normally. ("BOOT" LED 
also flickers.) 
5) "USER" 
LED 
ON 
: Error detected by CHK instruction or annunciator ON 
OFF : 
Normal 
Flicker  : Execution of latch clear 
6) "BAT." 
LED 
ON 
: Occurrence of battery error due to reduction in battery voltages of CPU module 
or memory card. 
OFF : 
Normal 
7) "BOOT" 
LED 
ON 
: Start of boot operation 
OFF 
: Non-execution of boot operation 
Flicker  : When automatic write to standard ROM is completed normally. ("ERR." LED 
also flickers.) 
8)  Module loading lever 