Справочник Пользователя для Panduit DPOE12U1XY

Скачать
Страница из 64
PANDUIT® DPoE™ Power Patch Panel User’s Guide 
Issue 2.2 
 
 
Part Number: PN378A 
 
 
 
 
 
  
18
 
 
LED Color 
Port LED Status 
Description 
Status of Power Ports 
Red 
Solid 
The system has failed to determine 
the PD power requirements for this 
port.  Perhaps this PD is not an 
802.3af-2003 compliant or Cisco 
legacy power device. It could also 
be a port configured for 802.3af-
2003 and an alternate PoE device 
has been connected.   
 
Also, pins (4,5) & (7,8) of a 
connected non-powered device 
such as a PC may be terminated in 
such a way that the power patch 
panel attempts to detect it as a PD. 
The Element Manager may be used 
to turn detection off (see Element 
Manager section) to this port so no 
further checks occur.  The LED will 
extinguish. 
 
This may also be an indication of a 
short in the wiring.  The connections 
at both ends of the horizontal 
cabling should be checked to 
ensure proper wiring has been 
followed. 
Power is NOT being 
delivered down this port on 
the panel. 
 
Table 10: Network Status LED Indications 
LED Color 
Network LED 
Status 
Description 
Notes 
Off 
Off 
No connection to the 
management system.   
If the system is otherwise operating 
normally and an Ethernet 10/100 cable 
is connected, this could be an issue 
with the panel's management interface.  
Green 
Flashing 
The management link on the 
DPoE™ Power Patch Panel 
is configured correctly and 
communication messages are 
currently being processed. 
Normal operation. 
Green 
Solid 
The management link on the 
DPoE™ Power Patch Panel 
is configured correctly, but no 
communication messages are 
currently being processed 
(i.e., the link is idle). 
Normal operation. 
Amber 
Solid 
The panel is currently trying 
to acquire DHCP address 
information from the network. 
If this persists for more than a minute or 
two, the daisy chain of connections 
between multiple panels may be 
incorrect or there are problems at the 
DHCP server.