Справочник Пользователя для Mitsubishi Electronics QSPCU

Скачать
Страница из 224
12
 - 1
12.1 Troubleshooting Basics
 
12
TROUBLESHOOTING
CHAPTER12  TROUBLESHOOTING
This section describes the various types of trouble that occur when the system is 
operated, and causes and remedies of these troubles.
12.1  Troubleshooting Basics
In order to increase the reliability of the system, not only highly reliable devices are used 
but also the speedy startup of the system after the occurrence of trouble becomes an 
important factor.
To start up the system speedily, the cause of the trouble must be located and eliminated 
correctly.
The basic three points that must be followed in the troubleshooting are as follows.
(1) Visual inspection
Visually check the following.
1) Movement of sequencer (stopped condition, operating condition)
2) Power supply on/off
3) Status of input/output devices
4) Installation condition of the power supply module, CPU module, intelligent 
function module to the base unit
5) Status of wiring (power cables, CC-Link dedicated cables)
6) Display status of various types of indicators ("POWER" LED, "RUN" LED, 
"ERR." LED)
7) Status of setting of various types of set switches
After checking 1) to 7), connect GX Developer and monitor the operating 
condition and program contents of the programmable controller.
(2) Check of trouble
Check to see how the operating condition of the programmable controller varies while 
the programmable controller is operated as follows.
1) Set the CPU module RUN/STOP/RESET switch to "STOP".
2) Reset the trouble with the CPU module RUN/STOP/RESET switch.
(
3) Turn ON and OFF the power supplied to the power supply module.
(3) Narrowing down the range of trouble occurrence causes.
Estimate the troubled part in accordance with items (1) and (2) above.
1) programmable controller or external devices
2) CPU module or others
3) Sequence program