12.2 Troubleshooting Flowchart
12.2.2 Flowchart for when the ERR terminal (negative logic) is off (opened)
12
TROUBLESHOOTING
12.2.2  Flowchart for when the ERR terminal (negative logic) is off (opened)
The following shows the flowchart for when the "ERR terminal" is off (opened) at power-on 
or during operation of the programmable controller.
The ERR terminal has
 turned off (opened).
Remove the corresponding power 
supply module, and mount it to the 
normal base unit. 
(Do not mount any modules other 
than the power supply module.)
Mount the corresponding power 
supply module to the original base 
unit again, and remove all modules 
other than the power supply module 
from the base unit.
NO
Flashing (CPU 
module is in stop 
error)
Conduct PLC diagnostics with GX 
Developer to check error details and take 
action according to the details.
 On
The corresponding power supply module is 
faulty
(Replace it with a normal power supply 
module). 
How is the "ERR." 
LED of the CPU 
module?
Not flashing
YES
How is the "ALIVE" 
LED of the CPU 
module?
Off
Supply power of proper voltage.
Is power supplied? 
Is the power supply 
voltage proper?
Off
On
How is the "POWER" LED 
of the power supply 
module?
(To next page)