Справочник Пользователя для Mitsubishi Electronics QSPCU

Скачать
Страница из 224
12
TROUBLESHOOTING
12.3 Error Code List  
12.3.4  Error code list (2000 to 2999)
12
 - 34
9
EM
C AN
D
 L
O
V
O
LT
AG
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND 
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
 AND 
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
 A
PPE
NDICES
 INDEX
 
 
2500
• There is a program file that uses a 
device that is out of the range set in 
the PLC parameter device setting.
Read the common information of the 
error using the GX Developer, check to 
be sure that the parameter device 
allocation setting and the program file 
device allocation correspond to the 
numerical values there (file name), and 
correct if necessary.
QS
2501
• More than two program files exist for 
one drive.
• The program name differs from the 
program contents.
• Delete unnecessary program files.
• Match the program name with the 
program contents.
QS
2502
The program file is incorrect.
Alternatively, the file contents are not 
those of a sequence program.
Check whether the program version 
is
.QPG, and check the file 
contents to be sure they are for a 
sequence program.
QS
2503
There are no program files at all.
(A drive No. is only displayed on the 
common information.)
• Check program configuration.
• Check parameters and program 
configuration.
QS
Error 
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding 
CPU