Chapter 4 - Signals and Troubleshooting 
 
 
 
IV A
  
4 - 2 
DCS 500B / DCP 500B Operating Instructions 
 
4.2 General messages 
 
 
The general messages will only be shown on the seven segment 
display of the control board SDCS-CON-x. 
 
Code 
 seven 
segm. 
display 
Text on  
LCD of control panel 
CDP 31x 
Definition 
 
Remark
8
 
Not available 
Program is not running 
– 
(1)
 
Not available 
Normal situation, no fault / no alarm signal 
– 
 
Not available 
Indication while loading another firmware 
into the drive 
– 
 
 
(1)   Units should be switched off and on electrically; if fault occurs again, the PCBs SDCS-POW-1 and SDCS-CON-x  
 
have to be checked and if necessary to be changed. 
 
 
4.3 Starting errors (E) 
 
 
The starting errors will only be shown on the seven segment display 
of the control board SDCS-CON-x. 
With starting errors it will not be possible to start the drive. 
 
Code 
 seven 
segm. 
display 
Text on  
LCD of control panel 
CDP 31x 
Definition 
 
Remark
E1 
Not available 
ROM memory test error 
– 
(1)
 
E2 
Not available 
RAM memory test error 
– 
(1)
 
E3 
Not available 
No TC-link board 
(not valid for software version S21.1xx) 
– 
 
E4 
Not available 
Communic. board SDCS-COM-x faulty 
– 
(2)
 
E5 
Not available 
No control program in memory 
– 
(3)
 
E6 
Not available 
ASIC not O.K.  
– 
(1)
 
E7 
Not available 
Parameter FLASH identity test failed  
– 
(1)
 
 
(1)   Units should be switched off and on electrically; if fault occurs again, the PCBs SDCS-POW-1 and SDCS-CON-x  
 
have to be checked and if necessary to be changed. 
(2)   Check communication board, plug in correctly
 
and if necessary change the board. 
(3)   Load firmware once more. 
 
 
 
3ADW000055R0401_DCS500B_Operating Instruction_e_d