Chapter 4 - Signals and Troubleshooting 
 
 
 
DCS 500B / DCP 500B Operating Instructions
 
IV  A
 
4 - 3 
 
4.4 Fault Signals (F) 
 
 
 
The fault signals will be shown on the seven segment display of the 
control board SDCS-CON-x as codes F . . as well as on the LCD of 
the control panel CDP 31x as clear text. 
All fault signals - with the exception of 
F 17
F 18
 and 
F 44
 - can be 
reset (after elimination of the faults); 
F 20 
would be
 
self resetting, if 
the communication had been re-established before. 
For resetting (RESET) of fault signals the following steps are re-
quired: 
• 
Switching off the commands ON/OFF and RUN 
• 
Elimination of the faults 
• 
Fault acknowledgement, i.e. resetting (RESET) 
  
a)  as described for CDP 31x 
 
or
 
b) by short-time setting of the command RESET  
  
  to high (logical one) via a binary input  
  
  (default setting = DI6). 
• 
Depending on the application conditions generate the commands 
ON/OFF and RUN once more. 
The fault signals will result in switching off the signal
 [10910]
 resp. in 
stopping the drive (installation-dependent). 
If a fault occurs, there will be three different possibilities of reaction (see 
column “Remark” in the fault list): 
(1) Fault will switch off the signals
 
energizing the main contactor, the field 
contactor and the fan contactor. 
(2) Fault will switch off the signals
 
energizing the main contactor and the 
field contactor. 
(3) Fault will switch off at least the signal
 
energizing the main contactor.
 
 
Code 
 seven 
segm. 
display 
Text on  
LCD of control panel 
CDP 31x 
Definition / 
 Action 
Status
 
signal
 
(FAULT_WORD_1/2) 
 
Remark 
F 1 
Auxil. undervoltage 
Auxiliary voltage fault 
Try to reset. Check internal auxiliary volt-
ages;
 
if fault persists, change SDCS-CON-x 
and/ or SDCS-POW 1 board (if required). 
11101
 
bit 0 
(1)
 
F 2 
Overcurrent 
Overcurrent
 
Check:  - Motor, load and armature cabling 
 
 
  for faults or blocking condition; 
 
 
- Parameter setting of current con- 
 
 
  trol circuit/torque limitation; 
   - 
Parameter
 [P 512]
  
    
(overcurrent 
detection). 
11101
 
bit 1 
(3)
 
3ADW000055R0401_DCS500B_Operating Instruction_e_d