Справочник Пользователя для AEG Protect 1.150

Скачать
Страница из 64
 
 
55 
 
This results in the following constellations with n+x technology: 
1 + 0  Use of 1 unit
 
max. 10, 15  or  
20 kVA
 
No redundancy
 
1 + 1  Use of 2 units
 
max. 10, 15  or  
20 kVA
 
Single redundancy
 
1 + 2  Use of 3 units
 
max. 10, 15  or  
20 kVA
 
Double redundancy 
(max. expansion level)
 
2 + 0  Use of 2 units
 
max. 20, 30  or  
40 kVA
 
No redundancy
 
2 + 1  Use of 3 units
 
max. 20, 30  or  
40 kVA
 
Single redundancy 
(max. expansion level)
 
3 + 0  Use of 3 units
 
max. 20, 30  or  
40 kVA
 
No redundancy (max. 
expansion level)
 
 
The actively redundant parallel operation automatically switches 
to power-increasing operation if the output power requirement 
exceeds the UPS single block power, i.e. the degree of 
redundancy is decreased or is completely eliminated. 
Conversely, the active UPS redundancy degree automatically 
increases again when the power consumption decreases. 
The connection normally takes place in the low-voltage main 
distribution, which also contains the external manual bypass 
and the following subdistribution of connected load circuits. 
Such a parallel board can be purchased in a wall housing incl. 
external HU as well as feeder and load distribution board from 
AEG Power Supply Systems via your specialist dealer. 
9.2 
Set-up / Connection of Parallel Operation Board 
The mains connection of each individual UPS takes place in the 
same way as described in chapter 5. 
 
The three-phase mains connection secured for 
each UPS must always have the same phase 
sequence, i.e. all UPS units are supplied at the 
input terminals L1, L2 and L3 by the same 
phase each time (no mix!). 
In UPS bypass mode, the phase L1 is used to 
connect the single-phase load with the mains. 
The central external manual bypass, which must 
have an all-pole design, must also be supplied 
by this phase L1.