Operation of the UPS in a parallel system 
The start-up process is uncomplicated, does not require any 
prior knowledge and is basically oriented to the procedure 
described in chapter 6. If you have obtained the parallel 
operation board from AEG Power Supply Systems, you can find 
further special instructions there. The displays in the parallel 
system function the same way as described for the individual 
UPS units in chapter 8. 
9.3.1 Start-Up 
13. 
Make sure that all connections have been made 
according to the installation instructions. 
14. 
Make sure that all loads are switched off. 
15. 
Make sure that all “maintenance switch” manual 
bypass switches (no. 3, p. 27/28) on the back of 
each UPS are in the “Bypass” position and all mains 
input miniature circuit breakers (no. 2, p. 27/28) on 
the back of each UPS are in the “OFF” position. 
16. 
Check the position of the central external manual 
bypass. This must be in the “Bypass” position, i.e. 
supply of the load busbar by the supplying mains. 
17. 
Now close all isolators in the output of each UPS, 
i.e. connect the output of each UPS with the parallel 
operation busbar.  
18. 
Now insert the back-up fuses in your low-voltage main 
distribution (where the central external manual bypass 
as well as the individual UPS systems are connected 
to the mains on the input side) or switch on the 
corresponding line protection switches there.  
i
 
The load supply now takes place via the central 
external manual bypass, and the parallel 
operation busbar is supplied with power via the 
integrated manual bypasses of each UPS. 
However, the parallel operation busbar and load 
busbar are not yet connected to each other at 
this time!