5.2.2 
Connection diameter and protection 
Please gather the minimal dimensions from the following 
table: 
Type PROTECT 
C. 6000 (S) 
C. 10000 (S) 
Diameter 
Mains line 
Loads connector 
 
6 mm
2
 
6 mm
2
 
 
10 mm
2
 
10 mm
2
 
Protection 
Mains fuse 
 
32 A 
 
50 A 
Table 1: Connection diameter and protection  
5.3 
One phase mains connector 
5.3.1 
Preparation for the one phase mains connector 
Before starting the connection tasks check that: 
♦  the values of the mains voltage (input voltage) and 
frequency complies with the values on the label on the 
UPS, 
♦  the grounding connection complies with the IEC norms 
or with the regional regulations, 
♦  the UPS is connected to the mains via a separate and 
fused line in a preswitched NS distribution, 
♦  the prefuse or the power fuse in the NS distribution has 
the same or higher value as indicated on the label on 
the rear of the UPS appliance, 
♦  the connection line from the prefuse to the UPS has to 
have a minimal diameter as defined in table 1: 
„Connection diameter and protection“ 
 
The UPS carries high voltage. The unit may only 
be installed or opened by trained and qualified 
personnel. Repairs may only be carried out by 
qualified customer service staff!