To change the other parameters (Second Level) follow these steps: 
 
Step 1 
 and 
 
Press and hold SET and DOWN for 10 seconds. The display 
will show 
dSPL
 
Step 2 
 
Press SET to change the parameter 
Step 3 
 or 
 
Press UP or DOWN to change the options, time or temperature 
for the current parameter  
Step 4 
 
Press SET to accept the new value 
Step 5 
 
Press DOWN to go to the next parameter, then go back to Step 
2. After the last parameter is displayed (
ALHi
), the display will 
go back to the normal operating condition 
 
Note: to scroll down the parameters without changing them, press the DOWN button. 
 
List of Parameters 
Here is a list of the parameters that can be changed in the Second Level of programming, as well as 
their options and ranges.  
Note:  Master-Bilt’s Set point Temperature (
Set)
 is set at a recommended –10
°
F at the 
factory.  
 
 
Parameter Displa
Symbo
Description 
Range / Options 
Master-
Bilt’s 
Factory 
Setting 
Display Status 
dSPL 
Information shown 
on the display 
during operation 
conditions  
tdAy
 – time-of-day 
rSP
°
 – zone temperature  
CyCL 
– cycle between time and 
zone temperature 
Epr
°
 
– evaporator coil temperature 
 
rSP 
Clock Format 
CLHr 
Time Format(12 or 
24 hours mode) 
12Hr
 – AM/PM format 
24Hr
 – 24 hour format  
12Hr 
Temperature 
Format 
°
dSP 
Temperature 
degrees 
°
F
 – degrees Fahrenheit 
°
C
 – degrees Celsius 
°
Defrost Type 
dFtP 
Type of defrost used 
in the application 
ELEC
 – electric defrost / off cycle 
HgAS
 – hot gas defrost  
ELEC 
Fan Status 
During Defrost 
EFAN 
Enable or not the 
fan during defrost 
no
 – fan is turned off during defrost 
yES
 – fan remains on during defrost  
No 
– for LT 
yES
–for MT
 
Fan Status 
During Normal 
Mode
 
CFAN 
Enable or not fan during 
normal compressor 
on/off mode
 
on 
– fan on during normal mode
 
CyCP 
– fan cycles with compressor
 
on 
Defrost 
Interval  
dFin 
Type of defrost 
interval 
TdAy
 – time-of-day setpoint 
CPrn
 – compressor run time 
tdEF 
– temperature initiated defrost 
ddEF 
– demand initiated defrost 
ddEF
–for LT
 
CPrn
–for MT
 
 
 
Minimum 
Compressor 
Off Time 
CoFF 
Minimum time that 
the compressor  
remain turned off  
Range: from 0 to 15 min  
2 min.