Minimum 
Compressor 
On Time 
Con 
Minimum time that 
the compressor 
remain turned on  
Range: from 0 to 15 min  
2 min. 
Alarm Delay 
ALrd 
Time delay before 
the alarm goes off 
after the 
temperature fall 
off the two alarm 
set points 
Range: from 0 to 59 min  
30 – for LT 
45 
– for MT 
Compressor 
Run Time 
CPrn 
Time the 
compressor runs 
between defrosts 
 
12 – for MT 
Number of 
Defrosts 
nodF 
Number of defrosts 
per day 
from 0 to 8 (0 means 1 defrost 
every 48 hours)  
N/A – for LT 
– for MT 
Defrost Start 
Time 
dEF1-8 
Start time of each 
defrost 
 
N/A 
Defrost 
Duration 
dEFd 
Defrost duration 
time (back-up for 
defrost 
termination 
temperature) 
Range: from 0 min to 4 hours 
35 – for LT 
– for MT 
Fan Delay 
FAnd 
Delay time for the 
fan after defrost 
(back-up for fan 
cut-in 
temperature) 
Range: from 0 to 15 min  
– for LT 
– for MT 
Pump Down 
Pudn 
Pump down duration  Range: from 0 to 59 min  
0 min. 
Drip Time 
driP 
Drip time duration 
Range: from 0 to 59 min  
– for LT 
– for MT 
Setpoint 
Differential 
diF
°
 
Cut-in temperature 
differential  
Note: cut-in is cut-
out plus differential 
Range: from 1 to 25
°
  
10
°
 F–for LT 
7
o
– for MT 
Temperature 
Initiated 
Defrost 
tdEF 
Temperature that 
will initiate a 
defrost cycle 
Range: from – 40 to 40
°
F or – 40 to 
4
°
N/A 
Defrost 
Termination  
Temperature 
dEF
°
 
Temperature in the 
evaporator that 
will terminate the 
defrost cycle 
Range: from 0 to 75
°
F or –18 to 
25
°
C  
50
°
 F 
Fan Cut-In 
Temperature 
FAn
°
 
Temperature in the 
evaporator that 
will turn the fan 
on after defrost 
Range: from – 40 to 60
°
F or – 40 to 
23
°
30
°
 F–for LT 
60
o
F–for MT 
Low 
Temperature 
Alarm  
ALLo 
Low temperature 
setpoint that will 
make the alarm go 
off and the error 
message appear on 
the display 
Range: from – 40  to 83
°
F or – 40 to 
23
°
C  
-40
°
 F–for LT 
32
o
F–for MT