Справочник Пользователя для Honeywell W7750A

Скачать
Страница из 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
52
Occasionally, the PID parameters require tuning to optimize 
comfort and smooth equipment operation. This applies to the 
W7750A,B,C Controllers.
CVAHU Controllers are configured by E-Vision with default 
values of PID parameters as shown in Appendix C Table 21. If 
different values for these parameters are desired, Table 13 
lists some recommended values to use as a starting point. 
These recommended values are based on past experience 
with the applications and in most cases do not require further 
adjustment.
Table 13. Recommended Values For PID Parameters.
If the PID parameters require adjustment away from these 
values, use caution to ensure that equipment problems do not 
arise (see CAUTION below). If any change to PID control 
parameters is made, the adjustments should be gradual. After 
each change, the system should be allowed to stabilize so the 
effects of the change can be accurately observed. Then 
further refinements can made, as needed, until the system is 
operating as desired.
CAUTION
If large or frequent changes to PID control parameters 
are made, it is possible to cause equipment problems 
such as short cycling compressors (if the stage 
minimum run times were disabled in User Addresses 
DisMinClTime or DisMinHtTime). Other problems that 
can occur include wide swings in space temperature 
and excessive overdriving of modulating outputs.
If adjustment of PID parameters is required, use the following. 
In the items that follow, the term, error, refers to the difference 
between the measured space temperature and the current 
actual space temperature setpoint.
— The Proportional Gain (also called Throttling Range) 
determines how much impact the error has on the output 
signal. Decreasing the Proportional Gain amplifies the 
effect of the error; that is, for a given error, a small 
Proportional Gain causes a higher output signal value.
— The Integral Gain (also called Integral Time) determines 
how much impact the error-over-time has on the output 
signal. Error-over-time has two components making up its 
value: the amount of time the error exists; and the size of 
the error. The higher the Integral Gain, the slower the 
control response. In other words, a decrease in Integral 
Gain causes a more rapid response in the output signal.
— The Derivative Gain (also called Derivative Time) 
determines how much impact the error rate has on the 
output signal. The error rate is how fast the error value is 
changing. It can also be the direction the space 
temperature is going, either toward or away from the 
setpoint, and its speed—quickly or slowly. A decrease in 
Derivative Gain causes a given error rate to have a larger 
effect on the output signal.
— The Control Band is used only for discharge temperature 
control of modulating outputs, which includes controlling 
the economizer dampers, and heating and cooling valves 
using Cascade Control. The Control Band dictates the 
span through which the discharge temperature must travel 
to cause the output signal to go from fully closed to fully 
open. Also, 10 percent of the Control Band value is the size 
of the deadband around the setpoint where no actuator 
motion occurs. For example, if controlling a cooling valve 
with Cascade Control enabled and with the discharge 
temperature within 0.1 X DaTempClCtrlBd of the discharge 
setpoint, there is no change in the current valve position.
The smaller the Control Band, the more responsive the 
control output. A larger Control Band causes more sluggish 
control. Be careful not to set the Control Band too low and 
cause large over or under shoots (hunting). This can 
happen if the space or discharge sensors or wiring are in 
noisy environments and the value reported to the controller 
is not stable (such that it bounces). The Control Band is 
used only in modulating control, and has no purpose when 
staged control is configured.
Appendix B. Sequences of Operation.
This Appendix provides the control sequences of operation for 
the models of the Excel 10 W7750 CVAHU Controller. The 
W7750A,B,C Controllers can be configured to control a wide 
variety of possible equipment arrangements. Table 14 and 15 
(copied from Tables 3 and 4) summarize the available options. 
This Appendix provides a more detailed discussion of these 
options.
Equipment Configuration
Heat 
Prop. 
Gain
Heat 
Integ. 
Gain
Heat 
Deriv. 
Gain
Heat 
Control 
Band
Cool 
Prop. 
Gain
Cool 
Integ. 
Gain
Cool 
Deriv. 
Gain
Cool 
Control 
Band
Econ 
Control 
Band
Single Stage
2
3000
0
10
2
3000
0
10
10
Two Stages
3
2000
0
10
3
2000
0
10
10
Three Stages
4.5
1500
0
10
4.5
1500
0
10
10
Four Stages
6
1000
0
10
6
1000
0
10
10
Series 60 Modulating (Floating)
2
750
0
10
2
750
0
10
10
PWM Modulating
2
900
0
10
2
900
0
10
10