EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
54
Table 15. Configuration Options Summary For W7750A,B,C Controllers.
ROOM TEMPERATURE SENSOR (RmTemp)
This is the room space temperature sensor. This sensor is the 
T7770 or the T7560A,B Wall Module. When it is configured, it 
provides the temperature input for the W7750 temperature 
control loop. If it is not configured, it is required that a room 
temperature sensor value be transmitted from another 
L
ON
W
ORKS
 Bus device. If no valid room temperature value is 
available to the W7750 Controller, the temperature control 
algorithm in the controller is disabled, causing the heating, 
cooling, and economizer control outputs to be turned off. If the 
W7750 Controller is configured for Continuous Fan (rather 
Option
Possible Configurations for the 
W7750A Model
Possible Configurations for the W7750B,C Models
Type of 
1. One stage.
1. One stage.
Heating
2. Two stages.
2. Two stages.
3. Three stages.
3. Three stages.
4. Four stages.
4. Four stages.
5. None.
5. Series 60 Modulating electric valve, or pneumatic via transducer.
6. Pulse Width Modulating electric valve, or pneumatic via transducer.
7. None.
Type of 
1. One stage.
1. One stage.
Cooling
2. Two stages.
2. Two stages.
3. Three stages.
3. Three stages.
4. Four stages.
4. Four stages.
5. None.
5. Series 60 Modulating electric valve, or pneumatic via transducer.
6. Pulse Width Modulating electric valve, or pneumatic via transducer.
7. None.
Type of 
Economizer
1. Digital Output Enable/Disable 
signal for controlling an external 
economizer package.
1. Digital Output Enable/Disable signal for controlling an external 
economizer package.
2. Series 60 Modulating electric 
damper motor, or pneumatic via 
transducer.
2. Series 60 Modulating electric damper motor, or pneumatic via 
transducer.
3. None.
3. Pulse Width Modulating electric damper motor, or pneumatic via 
transducer.
4. None.
IAQ Option
1. None.
1. None.
2. Local IAQ Digital Input—directly 
wired to the controller. (Contacts 
closed means poor IAQ is 
detected.)
2. Local IAQ Digital Input—directly wired to the controller. (Contacts 
closed means poor IAQ is detected.)
3. Network (IAQ Override signal 
received via the L
ON
W
ORKS
 Bus).
3. Network (IAQ Override signal received via the L
ON
W
ORKS
 Bus).
4. Local CO
2
 Analog Input—directly wired to the controller. (The sensor 
must be a 0 to 10V device representing 0 to 2000 PPM CO
2
.)
Coil Freeze 
1. None.
1. None.
Stat Option
2. Local Coil Freeze Stat Digital 
Input—directly wired to the controller. 
(Contacts closed means that coil 
freeze condition is sensed.)
2. Local Coil Freeze Stat Digital Input—directly wired to the controller. 
(Contacts closed means that coil freeze condition is sensed.)
Filter Monitor
1. None.
1. None.
Option
2. Local Dirty Filter Digital 
Input—directly wired to the 
controller. (Contacts closed means 
that the filter is dirty.)
2. Local Dirty Filter Digital Input—directly wired to the controller. 
(Contacts closed means that the filter is dirty.)
3. Local Analog Input for Differential Pressure across the Filter (directly 
wired to the controller). The sensor must be a 2 to 10V device 
representing 0 to 5 inw (1.25 kPa).