EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
53
74-2958—1
Common Operations
The Excel 10 W7750 Controller applications have many 
common operations that are applicable regardless of the type 
of heating, cooling, or economizer equipment configuration. 
These operations are available to the W7750A and the 
W7750B,C Versions of the CVAHU Controller, and the I/O and 
network configurations for them are summarized in Table 14.
Available input options are from the wall module and the 
hard-wired analog and digital inputs. Each application can 
have only a subset of these devices configured based on the 
number of physical I/O points available. However, some of the 
inputs are available over the L
ON
W
ORKS
 Bus network.
NOTE:
Each W7750 Controller must have a space 
temperature sensor input either wired directly to the 
controller, or shared from another L
ON
W
ORKS
 Bus 
device, and must have a digital output configured for 
controlling the supply fan. In addition, if modulating 
economizer control is desired, a discharge air 
temperature sensor must be physically connected to 
the Excel 10 W7750 Controller. A discharge 
temperature signal cannot be brought into the 
controller through the L
ON
W
ORKS
 Bus network.
Table 14. Common Configuration Options Summary For W7750A,B,C Controllers.
Option
Possible Configurations Common To All W7750 Models
Supply Fan 
1. Mandatory Digital Output.
Type of Air Handler
1. Conventional.
2. Heat Pump.
Occupancy Sensor
1. None.
2. Connected: Contacts closed equals Occupied.
3. Network (Occ/Unocc signal received via the L
ON
W
ORKS
 Bus network).
Window Sensor
1. None.
2. Physically Connected: Contacts closed equals window closed.
3. Network (Window Open/Closed signal received via the L
ON
W
ORKS
 Bus).
Wall Module Option
1. Local (direct wired to the controller).
(The T77560A,B has no L
ON
W
ORKS
 Bus access)
2. Network (sensor value received via the L
ON
W
ORKS
 Bus).
Wall Module Type
1. Sensor only.
(All wall modules have a L
ON
W
ORKS
 Bus access 
2. Sensor and Setpoint adjust.
jack except T7560A,B)
3. Sensor, Setpoint adjust and Bypass.
4. Sensor and Bypass.
Smoke Emergency Initiation
1. None.
2. Physically Connected: Contacts closed equals smoke detected.
3. Network (Emergency/Normal signal received via the L
ON
W
ORKS
 Bus).