User manual 
COMPACT V2.0 E 
17 
 
Note: In the Inverter operation, The COMPACT generates a true sinusoidal and quartz stabilized 
output voltage. When, however the COMPACT is supplied from a grid or a generator and the  
transfer contact is active, then you have at the output AC OUT the same voltage as that at the 
input. This voltage can not be modified by the COMPACT! 
4.7.1  Set the transfer voltage threshold 
The voltage threshold of the transfer can by adjust between 150 to 230V with the turning knobs 
(23). From factory this value is 200V. Majority’s of appliances can working on this voltage. When 
the Input voltages reach the settled value on turning knob, the inverter switch off and the AC 
INPUT go directly on the AC OUTPUT. When the voltage INPUT is less of 20V the value set, the 
transfer is stop and the OUTPUT switch back on the inverter.  
 
Don’t use the turning knobs “TRANSFERT” (23) to adjust the AC OUTPUT voltage! 
This is only it’s only a voltage threshold level to enable or disable the transfer. 
4.7.2  FAST (UPS)- MODE for the Transfer Switch 
The quick and break free Transfer mode is programmed with a slide switch „Transfer Delay“ OFF, 
which is on the front side (cable connections side). 
The aim of the COMPACT is to supply the consuming device with a break-free alternating voltage. 
When the incoming voltage AC IN no longer matches values which have been set with the Turning 
Knob 23, the Inverter switches on at once. The transfer is carried out in 0.02 seconds. This quick 
transfer ensure a break-free function for most consuming devices . If you have an alternating 
voltage back at the input AC IN, transfer system starts up again without any break, and the inverter 
is stopped.  
4.7.3  Delayed mode of the Transfer System 
The delayed mode of the transfer system „Transfer Delay ON“ is programmed with the slide switch 
on front with the cable connections. The COMPACT provides a break-free alternating voltage for 
the consuming device. A quick transfer switch is not always sensible nor is it always desired.  For 
example, when the consuming devices are operated by a small back-up generator. An overload of 
a short duration on such  a generator, i.e. start of a vacuum cleaner etc., has the effect of 
decreasing the voltage for a short time. As in such cases the transfer to the Inverter is not 
desirable, the transfer system can be programmed with a delay. When the slide switch (Transfer 
delay) is  in the „On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If 
the voltage falls below 100Vac, the transfer takes place without delay! The transfer switching to the 
Inverter takes place without any break. 
4.8  The Solar charge regulator (option) 
The COMPACT also has a Solar Charge Regulator built in. For charging the batteries, Solar 
modules can be connected to the screw terminal SOLAR +/-. The in-built regulator is a „Shunt 
regulator“ for the maximum input current of 30A for C1312 and C2324 and 20A for C3548. The 
operating voltage of  Solar panels to be connected must match the actual operating voltage of the 
COMPACT and never exceeds the max. rated value. 
 
Under no circumstances should any other systems such as wind-generator be connected at 
the input of the Solar Charge Regulator
The Solar Charge Regulator works automatically and is always in operation. As soon as the energy 
is delivered from the Solar Charge Regulator, LED 3 “SOLAR CHARGE” is lit and the batteries are 
being charged. The Solar Charge Regulator works even when the Battery Charger is functioning. 
The way of working is the principally the same as that of the Battery Charger. The function is 
described in the section on Battery Charger. The programming and the adjustments are carried out 
in accordance with the same conditions. Check with your battery supplier which adjustments must 
be carried out for your battery.  
4.9 The Multifunctional Contact 
In the COMPACT there is a built-in programmable power relay. The potential-free change-over 
contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT.