Справочник Пользователя для Studer Innotec C2324 COMPACT

Скачать
Страница из 23
STUDER INNOTEC 
   
                                                        
COMPACT
COMPACT
COMPACT
COMPACT
 
 
User manual 
COMPACT V2.0 E 
18 
 
Maximum Contact load: 
-230Vac /16Amp-30Vdc/1A! 
With the Push Button  21 „AUXILARY CONTACT“ the contact can be manually switched on or off 
independent of programming and the operating situation. The LED 5 “Contact active” show the 
state of the contact. The drawing up the screw terminal “AUX CONTACT”  is the inactive position 
mode, LED 5 “Contact active” off. 
The switching on and off of this contact can be freely programmed for every operating situation of 
the COMPACT witch situation is indicated with a LED. There is no limitation to its application and it 
is left to your wishes and desires as to where and how you would like to use it. The example and 
the setting of this contact are explain chapter  5.4.2. 
In factory we program this for a dysfunction alarm. The contact is active when one of these 
situations are detected:  
 
•  Over temperature (LED 10 lit) 
•  Overload (LED 11 lit) 
•  Over or less voltage of batteries (LED 12 lit or blink)  
•  COMPACT is turned off manually or with a fault (LED 13 lit) 
4.10 
The Remote Control
 
As an option a Remote Control can 
be connected to the COMPACT. All 
operating controls and displays 
except from level adjustment are 
available on the Remote Control. 
The Remote Control is supplied 
with a 20m long cable. It can 
lengthened to 40m. The Remote 
Control is suitable  for surface 
mounting on the wall or on to a 
switch board. It is fixed with 4 
screws. The COMPACT can also 
be  programmed with the Remote 
Control. The Programming is 
described in the section 
„Programming“. 
The output power and the charging 
currents are displayed on the 
Remote Control.  
 
In the Remote Control there is an 
additional Alarm Contact and a Control 
Input built in. These two functions are 
available through Tip-jack RJ11/4 for use. 
This Auxiliary Contact is Front / Work 
Contact (max. 0.5A!), which is 
independent of the Auxiliary Contact of the 
COMPACT. This contact is active in case 
of an alarm of the COMPACT. 
 
The Control Input is connected in parallel to the ON/OFF- push button. The COMPACT can be 
switched on or off through this input with an impulse button or an impulse contact. 
 
Order Number for Remote Control: RCC-01 
Dimensions: H x B x T / 111.5 x 136.5 x 25mm 
Caution: No external voltage should be connected to this Input Control. 
 
OFF
 
AC OUT
 
Over Temp.
 
Overload
 
AC IN
SOLAR CHARGE
Contact manual
Contact active
Program
COMPACT 
AUXILIARY  CONTACT
ON/
 
OFF
 
INVERTER - CHARGER
 
 
 
(Select)
 
RCC-01
INVERTER
 
CHARGER
(Program)
(Change status)
Battery
 
Low/High
 
RESET
 
ALARM
 
10
20
30
40
50
60
70
TRANSFER
 
Charger
Inverter
5
10
20
40
60
80
100
130
160
A
%
EQUALIZE
 
1 2 3 4
ON/
OFF
 
! -
batt
 ! 
R
e
m
o
te
 c
o
nt
or
60V/0,5A
 
max
.
Remote 
control
COMPACT
COMPACT
COMPACT
COMPACT
only 
Dry contact