10 - 18 
MELSEC-A
10   ADVANCED POSITIONING CONTROL 
 
The setting requirements and details of the following "condition data" 
Da.15  to 
Da.18   setting items differ according to the " Da.14   Condition target" setting.   
The following shows the  Da.15  to  Da.18   setting items corresponding to the 
" Da.14  Condition target". 
 
Other setting 
item 
Da.14   
Setting item 
Da.15  Condition 
operator 
Da.16
 
Address
Da.17  Parameter 1 
Da.18  Parameter 2 
01
H
: Device X 
07
H
 : DEV=ON 
08
H
 : DEV=OFF 
– 
0
H
 to F
H
 (bit No.) 
– 
02
H
: Device Y 
10
H
 to 1F
H
 (bit No.) 
03
H
: Buffer memory 
(1 word)
*1
 
01
H
 : 
=P1 
02
H
 : 
P1 
03
H
 : 
P1 
04
H
 : 
P1 
05
H
 : P1
P2 
06
H
 : 
P1, P2 
Buffer 
memory 
address 
P1 (numeric value) 
P2 (numeric value) 
(Set only when  Da.15  is 
[05
H
] or [06
H
].) 
04
H
: Buffer memory 
(2 words)
*1
 
05
H
: Positioning data 
No.
*2
 
09
H
 : Axis 1 designation 
0A
H
 : Axis 2 designation 
— 
Low-order 
16 bits 
Axis 1 positioning 
data No. 
Low-order 
16 bits 
– 
High-order 
16 bits 
Axis 2 positioning 
data No. 
High-order 
16 bits 
– 
 
– 
:  Setting not required (Setting value will be ignored. Use the initial value or a value within the setting range.) 
  :  Value stored in buffer memory designated in 
Da.16
.  
*1 
:  The comparison operators   and   are interpreted with the equal sign working.   
*2 
:  For the starting axis (axis where positioning start takes place), set the value to 0. A value other than 0 results in the 
processing of the positioning data set in " Da.17   Parameter 1" and " Da.18   Parameter 2" instead of "
Da.11
 
Start data No.".