12 - 52 
MELSEC-A
12   CONTROL AUXILIARY FUNCTIONS 
 
Example 3 
(1)  The conditions for calculation of the positioning address are indicated below. 
 Movement amount per pulse: 0.9 ( m) 
 Zero point address: 0.0 ( m) 
 Number of feedback pulses: 8192 (pulse) 
 
(2)  Calculate the positioning address from the range of using the number of output 
pulses in Condition 1 and the expression of calculating the positioning address 
(Expression 1). 
 Lower limit value of positioning address (calculated with the number of 
negative side pulses in Condition 1) 
(Positioning address) = (movement amount per pulse)   (number of output 
pulses) + (zero point address) 
= 0.9   (–268435456) + 0.0 
= 241591910.4 ( m) 
 Upper limit value of positioning address (calculated with the number of 
positive side pulses in Condition 1) 
(Positioning address) = (movement amount per pulse)   (number of output 
pulses) + (zero point address) 
= 0.9   268435455 + 0.0 
= 241591909.5 ( m) 
 
(3)  Since the calculated upper and lower limit values of the positioning address 
are outside the range of Condition 2, use the positioning address in the 
positioning range (–214748364.8 ( m) to 214748364.7 ( m)) of Condition 2. 
 
Zero point
0
-214748364.8
Unit:   m
Range unusable in absolute position
detection system
-241591910.4
241591909.5
214748364.7
Setting disabled
Setting disabled
 
 
2. Concept when the unit is degree 
 The positioning address is within the range 0  to 359.99999  of the position 
reached by a zero point return. 
When the zero point position is not 0 , the range is also 0  to 359.99999 . 
 
 When positioning is performed in the same direction, control beyond the limit value 
(when the address increases: 359.99999    0 , when the address decreases: 0  
 359.99999 ) cannot be carried out. (See below) 
 
0
0
359.99999
359.99999
Zero point
Unusable in absolute position detection system.
At power on or reset, current value cannot be
restored normally.
Unusable in absolute position detection system.
At power on or reset, current value cannot be
restored normally.
Range usable in absolute position detection system.
(0  to 359.99999 )
 
 
 For use in the absolute position detection system, set the upper and lower limit 
values of the software stroke limit within the range 0  to 359.99999 .