12 - 71 
MELSEC-A
12   CONTROL AUXILIARY FUNCTIONS 
 
(3)   Setting the command in-position function 
To use the "command in-position function", set the required value in the 
parameter shown in the following table, and write it to the D75P2.  
The set details are validated at the rising edge (OFF   ON) of the remote station 
READY signal [RX(n+7)B]. 
 
Setting item 
Setting 
value 
Setting details 
Factory-set 
initial value 
Pr.17  
Command in-
position width 
 
Turn ON the command in-position signal, and set the 
remaining distance to the stop position of the position 
control. 
100 
 
                  * Refer to section "5.2 List of parameters" for setting details. 
 
(4)   Confirming the command in-position signal 
The "command in-position signal" is stored in the following remote input/output.  
 
Monitor item 
Monitor 
value 
Storage details 
Remote input/output 
Axis 1 
Axis 2 
Command in-position 
signal 
 
OFF: Outside in-position range 
ON: Within in-position range 
RX(n+1)E RX(n+4)E
 
                  * Refer to section "3.4 Specifications of input/output signals for master module" for information on the storage 
details. 
 
 
REMARK 
 Parameters are set for each axis.