14 - 6 
MELSEC-A
14   TROUBLESHOOTING 
 
 Warning storage 
 
(1)  When an axis warning occurs, the warning code corresponding to the warning 
details is stored in the "Axis warning No. (RWrn+6, RWrn+14)" for axis 
warning No. storage. 
 
Axis No. 
Remote register 
1 RWrn+6 
2 RWrn+14 
 
(2)  When an axis warning occurs in a positioning operation, etc., "Axis warning 
detection (RX(n+2)1, RX(n+5)1)" turns ON. 
 
Axis No. 
Remote input/output 
1 RX(n+2)1 
2 RX(n+5)1 
 
(3)   Resetting errors and warnings 
When "Axis error reset (RY(n+2)4, RY(n+4)4)" is turned ON, the following 
processing is executed and the error warning status is then canceled. 
 
 "Axis error detection signal (RXnA, RXnB)" turned OFF 
 "Axis error No. (RWrn+5, RWrn+13)" cleared 
 "Axis warning detection signal (RX(n+2)1, RX(n+5)1)" turned OFF 
 "Axis warning No. (RWrn+6, RWrn+14)" cleared 
 Changing of the operation status from "error occurring" to "standing by".   
 Changing of the operation status from "step error occurring" to "standing by".   
 
(4)   Invalid operations 
For the following operations, the setting details will be invalidated, and an error or 
warning will not occur. 
 
 Speed change during machine zero point return 
 Speed change before operation (Speed override change, skip command, 
continuous operation interruption request) 
 Axis stop during axis stop 
 Axis sudden stop during axis stop 
 Axis stop before axis operation 
 Axis sudden stop before axis operation 
 
(5)      Checking the Error or Warning Number 
Use the following methods to check the error or warning number. 
 
(1)  “17-segment LED display function” on the front panel of main body of D75P2 
(Refer to section 13.4.) 
 
(2)    “Monitor function” of AD75 software package 
 
For details of (2), refer to the GPP Function Software Package Operating Manual 
or AD75 Software Package Operating Manual.