3   SPECIFICATIONS AND FUNCTIONS 
 
Item  
CC-Link station type 
Intelligent device station 
Number of occupied 
stations 
4 stations (RX/RY 128 points each, RWr/RWw 16 points each) 
External power supply (V)  24VDC (20.4 to 26.4VDC) 
Applicable conductor size 
(mm
2
0.75 to 2.00mm
2
 
Module mounting screw 
(mm) 
M4 0.7mm 16mm or more 
DIN rail can also be used for mounting. 
Applicable DIN rail 
TH35-7.5Fe, TH35-7.5AI, TH35-15Fe (compliant with JIS C 2812) 
Applicable crimping 
terminal 
RAV1.25-3.5, RAV2-3.5 
Internal current 
consumption (24VDC) (A) 
0.30A 
Flash ROM write count 
Maximum 100,000 times 
Noise immunity 
Noise voltage 500Vp-p, noise width 1s 
(by noise simulator of 25 to 60Hz noise frequency) 
Dielectric withstand 
voltage 
500VAC for 1 minute across power supply/communication system and external input/output 
Insulation resistance 
10M    or more by 500VDC insulation resistance tester across power supply/communication 
system and external input/output 
Outline dimensions (mm)  63.5 (H) 170 (W) 80 (D)mm 
Weight (kg) 
0.50kg 
 
      *
1
  When a stepping motor is used, the circular interpolation function cannot be used. 
      *
2
  The control unit of speed/position changeover control in the absolute system is "degree" only. 