3 - 19 
MELSEC-A
3   SPECIFICATIONS AND FUNCTIONS 
 
Device 
No. 
Signal name 
Details 
RX(n+1)E 
RX(n+4)E 
Axis 1 
Axis 2 
Command 
in-position 
signal 
OFF: Outside in-position 
range 
ON:   Within in-position 
range 
  This signal turns ON when the remaining distance falls within the 
"command in-position range" set in the parameter. 
  This signal turns OFF when the axis of the corresponding operation 
moves. 
  A command in-position check is performed every 56.8ms during position 
control. 
During speed control or during speed control of speed/position changeover 
control, a command in-position check is not performed. (*
1
RX(n+1)F 
RX(n+4)F 
Axis 1 
Axis 2 
Zero point 
return 
request flag 
OFF: Machine zero point 
return complete 
ON:   Machine zero point 
return being 
requested 
  This flag turns ON when any of the following conditions occurs, and turns 
OFF at completion of a machine zero point return. (*
1
(a) When the drive unit READY signal turns OFF 
(b) When the remote station READY signal turns ON 
(c) When a machine zero point return starts 
RX(n+2)0 
RX(n+5)0 
Axis 1 
Axis 2 
Zero point 
return 
complete 
flag 
OFF: Before machine 
zero point return 
completion 
ON:   After machine zero 
point return 
completion 
  This flag turns ON at normal completion of a machine zero point return. 
  This flag turns OFF at a machine zero point return start, positioning 
operation start, JOG operation start or manual pulse generator operation 
start or when the drive unit READY signal turns OFF. (*
1
RX(n+2)1 
RX(n+5)1 
Axis 1 
Axis 2 
Warning 
detection 
OFF: Without axis warning
ON:   With axis warning 
  This signal turns ON when an axis warning occurs. 
  This signal turns OFF when the axis error is reset. (*1) 
RX(n+2)2 
RX(n+5)2 
Axis 1 
Axis 2 
Speed 
change 0 
flag 
OFF:  New speed value is 
other than 0 
ON:   New speed value is 
  This signal turns ON when Speed change request (RY(n+2)7, RY(n+4)7) 
is turned ON at a new speed value of 0. 
  This signal turns OFF when Speed change request is turned ON at a new 
speed value of other than 0. (*
1
RX(n+2)3 
RX(n+5)3 
Axis 1 
Axis 2 
Zero point 
absolute 
position 
overflow flag 
OFF: Overflow not 
occurred 
ON:   Overflow occurred 
  This signal turns ON when the zero point absolute position (*
2
) has 
overflown due to a current value change. (*
1
RX(n+2)4 
RX(n+5)4 
Axis 1 
Axis 2 
Zero point 
absolute 
position 
underflow 
flag 
OFF: Underflow not 
occurred 
ON:   Underflow occurred 
  This signal turns ON when the zero point absolute position (*
2
) has 
underflown due to a current value change. (*
1
RX(n+2)5 
RX(n+5)5 
Axis 1 
Axis 2 
ABS data bit 
OFF: bitOFF 
ON:   bitON 
  This signal indicates the low-order bit of ABS data. (*
3
RX(n+2)6 
RX(n+5)6 
Axis 1 
Axis 2 
ABS data bit 
OFF: bitOFF 
ON:   bitON 
  This signal indicates the high-order bit of ABS data. (*
3
RX(n+2)7 
RX(n+5)7 
Axis 1 
Axis 2 
Transmissio
n data 
READY flag 
OFF: Trans-mission data 
being prepared 
ON:   Trans-mission data 
ready 
  This signal indicates the preparation condition of transmission data in the 
ABS transfer mode. (*
3
RX(n+2)8 
RX(n+5)8 
Axis 1 
Axis 2 
Restart 
acceptance 
complete flag 
OFF:  Restart not accepted
ON:   Restart accepted 
  This signal indicates a restart acceptance condition. 
Initial data processing request 
RX(n+7)8 Initial data 
processing request 
OFF:  No initial data 
processing request 
ON:   Initial data 
processing being 
requested 
  After power-on or after a hardware reset, the D75P2 turns ON Initial data 
request to request initial data setting. 
This signal turns OFF when Initial data processing complete (RY(n+7)8) 
turns ON. 
 
n: Address assigned to the master module by station number setting 
*
1
: Updated every 56.8ms. (Not update when processing is completed within 56.8ms.) 
*
2
: Refer to section 12.6 for the zero point absolute position. 
*
3
: Used for maintenance of the absolute position detection system. Unusable for normal operation.