3 - 20 
MELSEC-A
3   SPECIFICATIONS AND FUNCTIONS 
 
Device 
No. 
Signal name 
Details 
RX(n+7)9  Initial data setting 
complete 
OFF:  Initial data setting 
incomplete 
ON:   Initial data setting 
complete 
  This signal turns ON at completion of initial data setting after Initial data 
setting request (RY(n+7)9) has turned ON. 
When Initial data request (RX(n+7)8) turns OFF at completion of initial 
data setting, Initial data setting complete also turns OFF. 
RX(n+7)B  Remote station 
READY 
OFF: Positioning 
operation disable 
ON:   Positioning 
operation enable 
(a) This signal indicates that the D75P2 is ready for positioning operation. 
  This signal turns ON depending on ON/OFF of Initial data processing 
complete (RY(n+7)8) and Initial data setting request (RY(n+7)9). 
  This signal turns ON when positioning operation, zero point return, 
JOG operation or manual pulse generator operation is performed in the 
test mode of the peripheral device. 
(b) When any positioning parameter setting is to be changed, this signal 
must be turned OFF depending on the item to be changed. 
(c) When Remote station READY is turned from OFF to ON, the following 
processing is performed. 
  Parameter range check 
  The D75P2 READY signal (RXn0) is turned OFF. 
(d) When Remote station READY is turned from ON to OFF, the following 
processing is performed. 
  The D75P2 READY signal (RXn0) is turned ON. 
  The operating axes are stopped. 
  The M code ON signal of each axis is turned OFF and the M code 
storage area is cleared.