3 - 21 
MELSEC-A
3   SPECIFICATIONS AND FUNCTIONS 
 
3.4.3 Details of output signals (Master module   D75P2) 
The ON/OFF timing and conditions, etc., of the output signals are shown below. 
 
Device 
No. 
Signal name 
Details 
RY(n+1)0 
RY(n+1)1 
Axis 1 
Axis 2 
Positioning 
start 
OFF : No positioning 
start request 
ON : 
Positioning 
start 
requested 
  Zero point return or positioning operation is started. 
  The positioning start signal is valid at the rising edge, and carries out 
starting. 
  When the positioning start signal turns ON during BUSY, the warning “start 
during operation” (warning code: 100) will occur. 
RY(n+1)3 
RY(n+1)4 
Axis 1 
Axis 2 
Axis stop 
OFF  : No axis stop 
request 
ON : 
Axis 
stop 
requested 
  When the axis stop signal turns ON, the zero point return control, 
positioning control, JOG operation and manual pulse generator operation 
will stop. 
  By turning the axis stop signal ON during positioning operation, the 
positioning operation will be "stopped". 
  Whether to decelerate or suddenly stop for each stop group can be 
selected with "
Pr.38
 Stop group 1 sudden stop selection" to "
Pr.40
 
Stop group 3 sudden stop selection". 
  During interpolation control of the positioning operation, if the axis stop 
signal for either axis turns ON, both axes will decelerate and stop. 
RY(n+1)6 
RY(n+1)8 
Axis 1 
Axis 2 
Forward run 
JOG start 
Reverse run 
JOG start 
OFF  : JOG not started 
ON : 
JOG 
started 
  When the Forward run JOG start signal is ON, Forward run JOG operation 
will be carried out at the JOG speed. When the Forward run JOG start 
signal turns OFF, the system will decelerate and stop. 
RY(n+1)7 
RY(n+1)9 
Axis 1 
Axis 2 
Reverse run 
JOG start 
OFF  : JOG not started 
ON : 
JOG 
started 
  When the Reverse run JOG start signal is ON, Reverse run JOG operation 
will be carried out at the JOG speed. 
When the Reverse run JOG start signal turns OFF, the system will 
decelerate and stop. 
RY(n+2)0 
RY(n+4)0 
Axis 1 
Axis 2 
Servo ON 
OFF : Servo OFF 
ON : 
Servo 
ON 
  This signal turns ON when servo is to be switched ON. (*2) 
RY(n+2)1 
RY(n+4)1 
Axis 1 
Axis 2 
ABS 
transfer 
mode 
OFF : Non-ABS transfer 
mode 
ON  : ABS transfer mode
  This signal turns ON when the ABS transfer mode is to be selected. (*1) 
RY(n+2)2 
RY(n+4)2 
Axis 1 
Axis 2 
ABS 
request flag 
OFF : ABS data request 
acceptance 
complete 
ON  : ABS data being 
requested 
  This signal turns ON when ABS data is to be requested in the ABS 
transfer mode. (*1) 
RY(n+2)3 
RY(n+4)3 
Axis 1 
Axis 2 
Deviation 
counter 
clear 
OFF : Deviation counter 
clear request 
acceptance 
complete 
ON : 
Deviation 
counter 
clear being 
requested 
  This signal turns ON when the deviation counter of the servo amplifier is to 
be cleared. (*1) 
RY(n+2)4 
RY(n+4)4 
Axis 1 
Axis 2 
Error reset  OFF  : No error reset 
request 
ON : 
Error 
reset 
requested 
  This signal is used to clear the axis error detection, axis error number, axis 
warning detection and axis warning number. 
  This signal turns ON when ABS data is to be requested in the ABS 
transfer mode. 
  This signal changes the axis operation status from error occurrence to 
standby. (The signal does nothing during a start.) 
  This signal executes an error reset on its rising edge. (*3) 
RY(n+2)5 
RY(n+4)5 
Axis 1 
Axis 2 
Restart 
command 
OFF : No restart 
command 
ON : 
Restart 
commanded 
  Turning ON this signal when the axis operation status is a stop starts 
positioning from the stop position to the end point of the positioning data 
that caused the stop. 
  This signal executes a restart on its rising edge. (*3) 
RY(n+2)6 
RY(n+4)6 
Axis 1 
Axis 2 
M code 
OFF 
request 
OFF  : No M code OFF 
request 
ON  : M code OFF 
requested 
  M code OFF request turns OFF the M code ON signal (RXnD, RXnE). 
  This signal executes M code OFF on its rising edge. (*3) 
 
n: Address assigned to the master module by station number setting 
*
1
: Used for maintenance of the absolute position detection system. Unusable for normal operation. 
*
2
: Used for operation of the absolute position detection system. 
*
3
: Updated every 56.8ms. (Not updated when processing is completed within 56.8ms.)