Rev. 0508 
7
Access to TX valves and Drain Lines
Mechanical - Remove product from end of case. Remove 
product  racks.  Remove  refrigeration  and  drain  access 
panels (labeled). TX valve (mechanical only) and drain are 
located under each access panel at end of the case.
Electronic - The Electronic Expansion valve master and 
slave cylinder(s) are located within the electrical access 
panel(s).
Electronic Expansion valve (Optional)
A  wide  variety  of  electronic  expansion  valves  and  case 
controllers  can  be  utilized.  Please  refer  to  EEV  and 
controller  manufacturers  information  sheet.  Sensors  for 
electronic expansion valves will be installed on the coil inlet, 
coil outlet, and in the discharge air. (Some supermarkets 
require a 4th sensor in the return air). Case controllers will 
be located in the electrical raceway or under the case.
Thermostatic Expansion valve Location
This device is located on the same side as the refrigeration 
stub. A balanced port expansion valve model is furnished 
as  standard  equipment,  unless  otherwise  specified  by 
customer.
Expansion valve Adjustment
Expansion  valves  must  be  adjusted  to  fully  feed  the 
evaporator.  Before  attempting  any  adjustments,  make 
sure the evaporator is either clear or very lightly covered 
with frost, and that the fixture is within 10°F of its expected 
operating temperature.
Measuring the Operating Superheat
1.   Determine the suction pressure with an accurate 
pressure gauge at the evaporator outlet.
.   From a refrigerant pressure temperature chart, 
determine the saturation temperature at the 
observed suction pressure.
3.   Measure the temperature of the suction gas at the 
thermostatic remote bulb location.
4.   Subtract the saturation temperature obtained in step 
No.  from the temperature measured in step No. 3.
5.   The difference is superheat.
6.   Set the superheat for 5°F - 7°F. 
T-STAT Location
T-STATS are located under access panels on the end of 
the case.
Refrigeration (Cont'd)
Electrical
Wiring Color Code
CASE MUST BE GROUNDED
NOTE:   Refer to label illustrated above that is affixed to case 
to determine the actual configuration as checked in the 
“TYPE INSTALLED” boxes.
Electrical Circuit Identification
Standard lighting for all models will be full length fluorescent 
lamps located within the case at the top.
The  switch  controlling  the  lights,  the  plug  provided  for 
digital scale, and the thermometer are located at the rear 
of the case mullion.
The receptacle that is provided on the exterior back of these 
models is intended for computerized scales with a five amp 
maximum load, not for large motors or other high wattage 
appliances. It should be wired to a dedicated circuit.
Electrical Service Receptacles (When Applicable)
The receptacles located on the exterior of the merchandiser 
are intended for scales and lighted displays. They are not 
intended  nor  suitable  for  large  motors  or  other  external 
appliances.
BEFORE SERVICING
ALWAYS DISCONNECT ELECTRICAL
POWER AT THE MAIN DISCONNECT
WHEN SERVICING OR REPLACING ANY
ELECTRICAL COMPONENT.
This includes (but not limited to) Fans, Heaters
Thermostats, and Lights.