Typical In-line Blower Motor System 
Venting Installations:
Calculating Vent System Length
To calculate the length of the system you need, add the 
equivalent feet (meters) for each vent piece used in the system.
Vent Piece
Equivalent Length
45° elbow
2.5 ft (0.8 m)
90° elbow
5.0 ft (1.5 m)
The maximum equivalent vent lengths are: 
10" (25.4 cm) round vent - 60 ft (18.3 m)
Example Vent System:
The following example falls within the maximum recommended 
vent length.
1 - 90° elbow
= 5.0 ft (1.5 m)
1 - wall cap
= 0.0 ft (0.0 m)
8 ft (2.4 m) straight
= 8.0 ft (2.4 m)
Length of system
= 13.0 ft (3.9 m)
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in 
conformance with National Electrical Code, ANSI/NFPA 70 
(latest edition), or CSA Standards C22.1-94, Canadian Electrical 
Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local 
codes and ordinances.
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that 
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association 
1 Batterymarch Park 
Quincy, MA 02169-7471
CSA International 
8501 East Pleasant Valley Road 
Cleveland, OH 44131-5575
 
A 120 volt, 60 Hz., AC only, 15-amp, fused electrical 
circuit is required.
 
If the house has aluminum wiring, follow the procedure 
below:
1.  Connect a section of solid copper wire to the 
pigtail leads.
2.  Connect the aluminum wiring to the added section 
of copper wire using special connectors and/or tools 
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.
 
Wire sizes and connections must conform with the rating of 
the appliance as specified on the model/serial/rating plate. 
The model/serial/rating plate is located behind the filter on 
the rear wall of the range hood.
 
Wire sizes must conform to the requirements of the 
National Electrical Code, ANSI/NFPA 70 (latest edition), 
or CSA Standards C22. 1-94, Canadian Electrical Code, 
Part 1 and C22.2 No. 0-M91 (latest edition) and all local 
codes and ordinances.
A
A
B
B
F
G
D
A
A
B
C
D
A
A
H
E
A.  10" (25.4 cm) round vent
B.  Mount on top of ceiling joists.
C.  Roof caps
D.  Plywood (optional on 
some installations)
E.  Mount on underside of roof rafters.
F.  Mount from cross-members 
tied to trusses.
G. Duct horizontal; mount to 
crossmembers tied to trusses.
H.  Wall cap
90  elbow
6 ft (1.8 m)
2 ft
(0.6 m)
Wall cap
Roof Venting
Wall Venting
A.  Roof cap
B.  10" (25.4 cm) 
round vent
A.  Wall cap
B.  10" (25.4 cm) 
round vent