3  Commissioning 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
51
 
Buttons on the Basic Operator Panel 
Panel/Button Function 
Effects 
 
Indicates 
Status 
The LCD displays the settings currently used by the inverter. 
 
Start motor 
Pressing the button starts the inverter. This button is disabled by 
default. To enable this button set P0700 = 1. 
 
Stop motor 
OFF1  Pressing the button causes the motor to come to a standstill 
at the selected ramp down rate. Disabled by default; to 
enable set P0700 = 1. 
OFF2  Pressing the button twice (or once long) causes the motor to 
coast to a standstill. This function is always enabled. 
 
Change 
direction 
Press this button to change the direction of rotation of the motor. 
Reverse is indicated by a minus (-) sign or a flashing decimal point. 
Disabled by default, to enable set P0700 = 1. 
 
Jog motor 
Pressing this button while the inverter has no output causes the 
motor to start and run at the preset jog frequency. The motor stops 
when the button is released. Pressing this button when the motor is 
running has no effect. 
 
Functions 
This button can be used to view additional information.  
Pressing and holding the button for 2 seconds from any parameter 
during operation, shows the following:  
1.  DC link voltage (indicated by d – units V). 
2.  Output current. (A) 
3.  Output frequency (Hz) 
4.  Output voltage (indicated by o – units V). 
5.  The value selected in P0005 (If P0005 is set to show any of the 
above (1 to 4) then this will not be shown again).  
Additional presses will toggle around the above displays. 
Jump Function 
From any parameter (rXXXX or PXXXX) a short press of the Fn 
button will immediately jump to r0000, you can then change another 
parameter, if required. Upon returning to r0000, pressing the Fn 
button will return you to your starting point. 
Quit 
In case of a fault or alarm the 
 button resets the fault or alarm 
message on the operator panel display. 
 
Access 
parameters 
Pressing this button allows access to the parameters. 
 
Increase 
value 
Pressing this button increases the displayed value.  
 
Decrease 
value 
Pressing this button decreases the displayed value.  
Figure 3-5 