3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
52 
6SE6400-5CA00-0BP0  
Changing parameters with the BOP 
The procedure for changing the value of parameter P0004 is described below. 
Modifying the value of an indexed parameter is illustrated using the example of 
P0719. Follow exactly the same procedure to alter other parameters that you wish 
to set via the BOP. 
 
Changing P0004 – parameter filter function 
Step
 
 
Result on display 
Press 
 to access parameters  
 
 
Press 
  until P0004 is displayed 
 
 
Press 
 to access the parameter value level 
 
 
Press 
 or 
 to the required value 
 
 
Press 
  to confirm and store the value 
 
 
Only the command parameters are visible to the user. 
 
 
 
Changing P0719 an indexed parameter  
Selection of command/setpoint source 
Step
 
 
Result on display 
Press 
 to access parameters  
 
 
Press 
  until P0719 is displayed 
 
 
Press 
 to access the parameter value level 
 
 
Press 
 to display current set value 
 
 
Press 
 or 
 to the required value 
 
 
Press 
  to confirm and store the value 
 
 
Press 
 until r0000 is displayed 
 
 
Press 
  to return the display to the standard drive display (as 
defined by the customer) 
 
 
Figure 3-6 
Changing parameters via the BOP 
NOTE 
In some cases - when changing parameter values - the display on the BOP shows 
. This means the inverter is busy with tasks of higher priority.