Справочник Пользователя для National Instruments FP-3000

Скачать
Страница из 118
Chapter 2
Installation and Configuration
2-12
©
 National Instruments Corporation
Figure 2-12.  FP-3000 Connector Pinout
LED Indicators
The FP-3000 has four LED indicators: POWERNETWORK
PROCESS, and STATUS. Figure 2-13 shows the LEDs on the FP-3000.
Figure 2-13.  LEDs on the FP-3000
When power is applied, the POWER LED blinks green for approximately 
seven seconds during the power on self test. If the self test passes, the 
POWER LED turns solid green and the READY LEDs on each 
I/O module are lit green. If the self test fails, the POWER LED is lit red 
and the module enters an inactive state. 
1
2
3
4
5
6
7
8
9
NC
NC
NC
NC
NC
NC
NC
Data +
Data –
NC = No Connection
POWER
FF-H1 PORT
PROCESS
STATUS
NETWORK
POWER
FF-H1 PORT
PROCESS
STATUS
NETWORK