The multicolored PROCESS LED is used to indicate the current state of 
the processes being controlled by the FP-3000. When a PID function block 
on the FP-3000 module is in initialization, the light flashes green. When all 
the executing PID blocks on the FP-3000 are in Target mode, the light 
remains lit solid green. Any active alarm of priority greater than eight 
results in the light being lit red. For more information on PID blocks, refer 
to the section 
 in Chapter 4, 
.
Table 2-1 describes the NETWORK LED states.
The red STATUS LED is lit when the FP-3000 detects a failure. If 
STATUS is not lit, the FP-3000 has not detected a failure. The FP-3000 
indicates specific error conditions by flashing STATUS a specific number 
of times. Table 2-2 describes the STATUS LED flashing sequences and the 
corresponding error conditions.
Table 2-1.  Description of Fieldbus NETWORK LED States
NETWORK LED State
Meaning
Off 
Fieldbus port not receiving data.
Flashing green
Fieldbus port is currently the Link Active 
Scheduler on the Fieldbus segment. The 
FP-3000 module can control 
communications on the Fieldbus.
Steady green
Fieldbus port is a basic device. The 
FP-3000 cannot control communication 
on the Fieldbus.
Flashing red and green
Fieldbus port is seeing traffic but is at a 
default Fieldbus network address. You 
need to assign a permanent network 
address through a Fieldbus configurator.
Steady red
Fieldbus port encountered fatal network 
error. Check the Fieldbus network 
connections.