Appendix C
Fieldbus Parameters
©
 National Instruments Corporation
C-17
RCAS_OUT
The back calculation output used by the host when establishing a Remote 
cascade loop.
RESET
The time constant for the integral component of the PID block. It is 
measured in seconds per repeat.
RESTART
Allows the user to restart the device remotely. Table C-12 lists restart 
values.
Caution
Using 
Restart to Default
 causes all your configured parameters in the 
FP-3000 to revert to their factory default settings.
ROUT_IN
The cascade input set by a remote host. This is propagated to the output of 
the block when it is in 
ROut
 mode. If the block is in 
ROut
 mode and this 
parameter is not updated in 
SHED_ROUT
 time (a parameter in the resource 
block), the block enters mode shedding. Mode shedding allows the block to 
degrade from 
ROut
 mode into some higher priority mode. For more 
information on mode shedding, refer to Appendix D, 
.
ROUT_OUT
This is the back calculation output used by the host when trying to establish 
a remote output loop. While the loop is being established, it is the current 
value of the output channel and can be used by the host to initialize for 
smooth transfer of control.
Table C-12.  Restart Values
Value
Behavior
Restart 
Resource
Restarts the device.
Restart to 
Defaults
Restarts the device, restoring all parameter values to 
default values.
Restart 
Processor
Restarts the device as if the power was cycled.