Appendix C
Fieldbus Parameters
C-18
©
National Instruments Corporation
RS_STATE
The current state of the device. Table C-13 lists device states.
SAFEGUARD_CL
An interlock input. When in
Discret_State_1
, the output of the block is
forced closed (
Discret_State_0
). This interlock input has priority over
all other interlock inputs.
SAFEGUARD_OP
An interlock input. When in
Discret_State_1
, the output of the block is
forced open (
Discret_State_1
). This interlock input has priority over all
other interlock inputs except
SAFEGUARD_CL
.
SET_FSTATE
Allows the user to set the device faultstate to active. This, in turn, forces all
output blocks into their own faultstate behavior.
output blocks into their own faultstate behavior.
SHED_OPT
Controls the way blocks enter mode shedding. Each option listed below has
a companion
a companion
No Return
option. The
No Return
shedding options change
the target mode of the device to the shed mode and prevent the device from
re-entering
re-entering
RCas
or
ROut
mode after the shed condition has ended.
, for more information about mode shedding.
Table C-13. Device States
State
Meaning
Start/Restart
The device has just started a restart cycle.
Initialization
The device is performing startup
diagnostics.
diagnostics.
Failure
A hardware failure has been detected.
On-Line Linking
The device is online and waiting for new
parameter linkages to be established.
parameter linkages to be established.
On-Line
The device is online and in service.
Standby
The device is online, but currently out of
service.
service.