Appendix C
Fieldbus Parameters
C-18
©
 National Instruments Corporation
RS_STATE
The current state of the device. Table C-13 lists device states.
SAFEGUARD_CL
An interlock input. When in 
Discret_State_1
, the output of the block is 
forced closed (
Discret_State_0
). This interlock input has priority over 
all other interlock inputs.
SAFEGUARD_OP
An interlock input. When in 
Discret_State_1
, the output of the block is 
forced open (
Discret_State_1
). This interlock input has priority over all 
other interlock inputs except 
SAFEGUARD_CL
.
SET_FSTATE
Allows the user to set the device faultstate to active. This, in turn, forces all 
output blocks into their own faultstate behavior.
SHED_OPT
Controls the way blocks enter mode shedding. Each option listed below has 
a companion 
No Return
 option. The 
No Return
 shedding options change 
the target mode of the device to the shed mode and prevent the device from 
re-entering 
RCas
 or 
ROut
 mode after the shed condition has ended. 
Table C-14 lists shed conditions. Refer to Appendix D, 
, for more information about mode shedding.
Table C-13.  Device States
State
Meaning
Start/Restart
The device has just started a restart cycle.
Initialization
The device is performing startup 
diagnostics.
Failure
A hardware failure has been detected.
On-Line Linking
The device is online and waiting for new 
parameter linkages to be established.
On-Line
The device is online and in service.
Standby
The device is online, but currently out of 
service.