Input/output configuration
Senstar LM100 Product Guide
Page 63
Remote light activation
In both local control mode and remote control mode, the LM100 can be configured to have specific
luminaires activated from remote locations. In local control mode, a simple on/off switch in a
central control room can be connected to an Aux input on the gateway. When the switch is turned
on the aux input goes high and the luminaire zone that is specified to activate in response turns on
(Zone Light Activate on the Aux Config tab). In remote control mode a command from the host
SMS can activate a luminaire zone.
luminaires activated from remote locations. In local control mode, a simple on/off switch in a
central control room can be connected to an Aux input on the gateway. When the switch is turned
on the aux input goes high and the luminaire zone that is specified to activate in response turns on
(Zone Light Activate on the Aux Config tab). In remote control mode a command from the host
SMS can activate a luminaire zone.
Input wiring configurations
includes the selectable Aux input wiring configurations, and
includes the
selectable supervision resistor values.
CAUTION
The I/O port configuration jumpers must be correctly set according to
the specific function of each port (see
the specific function of each port (see
).
Note
Use ¼ W 1% supervision resistors (see
for recommended
resistor values).
Input option
UCM selection
Alarm relay Supervision
R1
R2
unsupervised
NO
---
---
---
single resistor
supervision
supervision
NO
cut
5.1 k
---
dual resistor
supervision
supervision
NO
cut & short
4.3 k
820
unsupervised
NC
---
---
---
single resistor
supervision
supervision
NC
short
5.1 k
---
dual resistor
supervision
supervision
NC
cut & short
5.1 k
820
Table 2: Selectable input configurations
R1 values (single resistor
supervision)
supervision)
R1 values (double resistor
supervision)
supervision)
R2 values (double resistor
supervision)
supervision)
820
1.1 k
820
1 k
2.2 k
1.1 k
1.1 k
4.3 k
2.2 k
1.2 k
4.7 k
3.3 k
1.5 k
5.1 k
5.6 k
2.2 k
5.6 k
3.3 k
4.7 k
5.1 k
5.6 k
4.7 k
5.1 k
5.6 k
Table 3: Selectable resistor values