Справочник Пользователя для Siemens OpenAir GND Series

Скачать
Страница из 7
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers 
Technical Instructions 
 
Document No. 155-746 
 
March 17, 2005 
 
 
Specifications 
Power supply 
Operating voltage 
24 Vac ±20%  
   
24 
Vdc 
+20%, 
-10% 
   
120 
Vac 
±10% 
   
230 
Vac 
±10% 
Frequency 50/60 
Hz 
Power consumption 
24 Vac/dc 
  running 
20 
VA/12W 
  holding 
VA/6W 
Power Consumption 
120 Vac/230 Vac 
  running 
20 
VA 
 
 
holding 
  9 VA 
Function 
Running torque 
53 lb-in (6 Nm) (minimum) 
Stall torque (minimum) 
160 lb-in (18 Nm) 
Torque reduction at elevated temperature 
Less than 10% 
Runtime for 90° 
15 seconds nominal 
 
closing (on power loss) with spring return 
15 seconds maximum 
Nominal angle of rotation 
95°  
Life Expectancy 
 
 
 
Minimum 35,000 full stroke cycles 
Mounting 
Damper shaft size 
.5-inch (12,7 mm) round 
Damper shaft length, minimum 
1.4-inch (36 mm)  
Housing 
Enclosure 
NEMA 1  
Material  
Die cast aluminum alloy 
Ambient conditions 
Operation 
0°F to 140°F (-18°C to 60°C) 
 
 
 
one time 350°F (177°C) 
Storage and transport 
–40°F to 158°F (–40°C to 70°C) 
Ambient humidity (non-condensing) 
Maximum 95% rh non-condensing 
Teflon® cable 
400°F (200°C) 
Agency certification 
   
UL873 
 
 
 
cUL C22.2 No. 24-93 
   
AS/NZS 
2064 
1/2:1997 
 
 
 
Conforms to CE requirements for the 
 
 
 
EMC and low voltage directives 
   
 
 
Australian Electromagnetic 
 
Compatibility (EMC) per AS/NZS 
 4251.1/2:1999 
(C-tick) 
 
Miscellaneous 
 
 
Pre-cabled connection 
18 AWG, 3 feet (.9 meter) 
 
 
 
3/8-in (.5mm) flexible conduit connector 
Dimensions 
9-in. × 3.25-in. × 3-in. D 
 
 
 
(229 mm × 83 mm × 76 mm) 
Weight  
≈4 lb (1.8 kg) 
Siemens Building Technologies, Inc. 
 
 
Page 3 of 7