OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers 
Technical Instructions 
 
Document No. 155-746 
 
March 17, 2005 
 
 
Wiring 
All wiring must conform to NEC and local codes and regulations.  
 
 
Function Color 
Supply Red 
Neutral Black 
Ground Green 
Wire Designations 
 
24 Vac/dc 
 
M
BLACK
(NEUTRAL)
RED
(SUPPLY)
GREEN
(GROUND)
EA0941R1
 
Figure 2. 
 
 
 
 
Function Color 
Line Black 
Neutral White 
Ground Green 
120 Vac 
 
M
WHITE
(Neutral)
BLACK (Line)
GREEN
(Ground)
EA1167R2
 
Figure 3. 
 
 
 
 
 
Function
Color 
Line Brown 
Neutral Blue 
Ground Green 
230 Vac 
 
M
BLUE
(Neutral)
BROWN (Line)
GREEN
(Ground)
EA0609R2
 
Figure 4. 
 
 
CAUTION: 
The actuator must be wired 
with a 230 Vac line with respect 
to neutral and the ground lead 
must be connected for proper 
protection of the actuator. Any 
other connection, such as 
phase-to-phase, can damage 
the actuator. 
Auxiliary Switches  
YELLOW
GRAY
85∞
5∞
EA1163R2
 
Figure 5. 
 
Switch 
Wire 
Color 
Switch 
Makes 
Switch  
Breaks 
5° 
Gray 
< 5° 
> 5° 
85° 
Yellow  > 85° 
< 85° 
 
NOTE
Both sets of contacts are open when actuator is  
between 5° and 85°. 
 
Siemens Building Technologies, Inc. 
 
 
Page 5 of 7