Technical Instructions  
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers 
Document No. 155-746 
 
March 17, 2005 
 
 
 
Accessories 
EA1
127R1
 
Figure 1. 
Electronic Fusible Link (EFL) 
ASK79.165 (165°F (74°C) operation) 
ASK79.212 (212°F (100°C) operation) 
ASK79.250 (250°F (121°C) operation) 
ASK79.350 (350°F (177°C) operation) 
NOTE: 
  Determine and order 
appropriate actuator before 
selecting EFL. 
Operation 
When power is applied, the actuator coupling moves toward the open position, "90°". 
The actuator opens in 15 seconds nominal, 90° at 60 Hz. In the event of a power failure 
or when operating voltage is turned off, the actuator returns to the "0" position. The 
return time is 15 seconds nominal for 90°. 
The National Fire Protection Association NFPA 92A Standard for Recommended 
Practice for Smoke-Control System and UL 864 Standard for Control Units and 
Accessories for Fire Alarm Systems, require weekly self-tests for dedicated smoke 
control equipment used in a smoke control system. The National Fire Protection 
Association NFPA 72 Standard for National Fire Alarm Codes states that all life-safety 
systems are to be functionally checked at least annually.  
The GND actuator does not require any periodic cycling to function properly as an 
integral part of an active smoke control damper system. Check the smoke control 
damper/actuator every time you functionally check your smoke detectors, emergency 
lights, and/or power generators for operation. 
 
Installation 
Refer to the installation instructions for detailed guidelines. (See 129-402) 
 
 
CAUTION: 
Read and carefully follow the Installation Instructions to avoid equipment 
damage. 